Installation
40
1SVC 440 795 M0100
Connect digital DC inputs
Use input terminals I1 to I12 , R1 to R12 to connect
pushbutton actuators, switches or 3 or 4-wire proximity
switches. Given the high residual current, do not use 2-wire
proximity switches.
Connect digital DC inputs to the basic unit
Figure 17: Connect digital inputs CL-DC1 and CL-DC2
Connect digital DC inputs to the expansion unit
CL-LE...DC2
Figure 18: Connect digital inputs CL-LER.18DC2, CL-LET.20DC
L01
L01
0 V l1 I2 I7
+...V
DC : +24 V
DA : +12 V
F1
+24 V
0V
R10R9R8R7R6R5R4R3R2R1E+ E-
R11
R12 0V0V+24V
Input 24 V 24 V
F1