ABB | SACE Emax 2
24 | © 2017 ABB | 1SDH000999R0002 - ECN000058721 - Rev. B
Emax E1.2 circuit-breakers | 6 - Installation
Mounting the fixed part of the
withdrawable circuit-breaker
Fix the fixed part to a horizontal surface using four M8 x 25 screws (see Figure 44). Tighten the screws with
tightening torque = 21 Nm - 186 lb.in.
Figure 44
Types of terminal
The following are the different types of terminal:
Figure 45 - F - HR - Horizontal rear IEC
Figure 46 - F - VR - Vertical rear IEC
Figure 47 - F - F - Front IEC-UL
Figure 48 - F - EF - Extended front IEC-UL
Continued on the next page