ABB | SACE Emax 2
62 | © 2017 ABB | 1SDH000999R0002 - ECN000058721 - Rev. B
Electronic accessories | 3 - Ekip Supply modules
Electronic accessories
3 - Ekip Supply modules
Description
The Ekip Supply is a power supply accessory module.
There are two types, depending on the input voltages to be supplied:
Ekip Supply 24-48Vdc.
Ekip Supply 110-240Vac/dc.
Compatibility
The modules can be installed in the presence of trip units of Ekip Dip, Ekip Touch, Ekip Hi‐Touch, Ekip G
Touch, and Ekip G Hi‐Touch trip units.
Electrical characteristics
The following table lists the electrical characteristics of the modules:
Module
Power supply
voltages
Frequency Power input Inrush current
Ekip Supply
24-48Vdc
21.5…53 V DC - Maximum 10W Maximum 2 A per 20 ms
Ekip Supply
110-240Vac/dc
105…265 V AC/DC 45…66 Hz Maximum 10 VA/W Maximum 2 A per 20 ms
Connections
The modules must be mounted on the terminal box of the circuit-breaker or of the fixed part of the withdrawable
circuit-breaker, in the first free slot.
Information on the assembly is available on the web site http://www.abb.com/abblibrary/DownloadCenter/,
in particular in the kit sheet 1SDH001000R0511.
An example with an E1.2 circuit-breaker in fixed and withdrawable versions is provided to the side.
The following is a view of the terminal block of the E1.2 circuit-breaker and the wiring diagram:
Uaux.
A3
110-240VAC/DC
A4
+/L
-/N
24-48VDC
Ekip Supply 24-48VDC
Ekip Supply 110-240VAC/DC
SUPPLY
K51
A)
**
I)
EKIP
32
K51
A1
XV
X
K1
K1
K1
K2
K2
K2
W3
W3
W3
W4
W4
W4
K1 K2
(B)(A)
(LOCAL BUS)
Q)
*
W2
W3 W4
Diagrams 32
For external wiring, AWG 22-16 cables with a maximum external diameter of 1.4 mm must be used.
Further information is available on page 59, or on the site http://www.abb.com/abblibrary/DownloadCenter/,
where the wiring diagram is available 1SDM000091R0001.
Signallings
A
The following table illustrates the possible signals, and their meaning:
Pos. Description
A
Power LED, green. The possible states are:
• Off: power supply absent.
• On fixed: power supply present.

Table of Contents

Other manuals for ABB SACE Emax 2