ABB | SACE Emax 2
Ekip Dip protection trip unit | 2 - Protections
41 | © 2017 ABB | 1SDH000999R0002 - ECN000058721 - Rev. B
Neutral and frequency
Adjusting of the neutral setting is used to customize the L, S and I protections on the Neutral pole with a
control factor different to the other phases.
NOTE: use the adjustment of the neutral setting only with four-pole or three-pole circuit-
breakers with external neutral: with three-pole circuit-breakers and neutral protection active,
the trip unit signals the absence of the current sensor.
The adjustment of the frequency is used in order to set the installation frequency (between 50 and 60 Hz).
Neutral parameters
The user can activate the protection and set the percentage for calculation of the protection thresholds.
Parameter Description
Enable
By setting the threshold dip-switches to the Off position, the protection on the
Neutral is disabled.
Threshold InN
It establishes the multiplication factor applied to the trip thresholds of the
protections:
• 50%: lowest trip thresholds for the neutral current.
• 100%: same trip thresholds for all poles.
• 200%: highest trip thresholds for the neutral current.
Limitations
The adjustment of the Neutral threshold to value of 200 % must be performed considering the following
formula: (I1 * InN) Iu.
I1 indicates the threshold of protection L in Amperes (example: In = 1000 A; I1 = 0.45 In = 450 A), InN is the
neutral threshold expressed as a multiplication factor (example: 2), Iu indicates the size of the circuit-breaker
(example: 1000 A).

Table of Contents

Other manuals for ABB SACE Emax 2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB SACE Emax 2 and is the answer not in the manual?

ABB SACE Emax 2 Specifications

General IconGeneral
BrandABB
ModelSACE Emax 2
CategoryCircuit breakers
LanguageEnglish

Related product manuals