Emax E1.2 circuit-breakers | 6 - Installation
Connection to the power circuit
The connection of a circuit-breaker to the power circuit is performed using the connection busbars of the
electric switchgear fixed to the terminals of the circuit-breaker. The sizing of the busbars is specified by the
designer of the electrical switchgear.
Figure 63
Figure 64
IMPORTANT: it is possible to obtain different capacities for the connections by altering
the thickness and number of busbars in parallel.
The following tables provide some examples of the quantity and the sizes of the connections that can be used
for each type of circuit-breaker:
circuit-breaker
IEC 60947
Iu (A)
Dimension of
busbars (mm)
Horizontal terminals Vertical terminals
E1.2 630 2x40x5 yes yes
E1.2 800 2x50x5 yes yes
E1.2 1000
2x50x10 yes -
2x50x8 - yes
E1.2 1250
2x50x10 yes -
2x50x8 - yes
E1.2 1600
3x50x8 yes -
2x50x10 - yes
circuit-breaker
UL 1066
Iu (A)
Horizontal terminals Vertical terminals
Q.ty Dimension of busbars (in) Q.ty Dimension of busbars (in)
E1.2-A 800 2 1/4 x 2 1 1/4 x 3
E1.2-A 1200 4 1/4 x 2 2 1/4 x 3