EasyManuals Logo
Home>ABB>Circuit breakers>SACE Emax 2

ABB SACE Emax 2 User Manual

ABB SACE Emax 2
109 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #85 background imageLoading...
Page #85 background image
ABB | SACE Emax 2
Electrical accessories | 2 - Electrical signalling accessories
83 | © 2017 ABB | 1SDH000999R0002 - ECN000058721 - Rev. B
S33 M/2: springs charged
signalling contact
The S33 M/2 contact signals the state of the closing springs of the circuit-breaker control (charged or
discharged).
It is available in two types:
standard contact
contact for digital signals
NOTE: the S33_M/2 contact is always included in the gearmotor for automatic charging of
the springs in the standard version. The version for digital signals must be requested with the
order for the motor.
The following table provides information on the electrical characteristics:
Characteristics Standard Digital signals
Breaking
capacity
DC
24V - 0.1 A
125V 0.5A @ 0ms / 0.3A @ 10ms -
250V 0.3A @ 0ms / 0.15A @ 10ms -
AC
250V
3A cos φ 0.3 -
5A cos φ 0.7 -
5A cos φ 1 -
400V
3A cos φ 1 -
2A cos φ 0.7 -
1A cos φ 0.3 -
Minimum load 100mA @ 24V 1mA @ 5V
S33/M2: Connections
38
36
35
S33
Further information is available on page 59, or on the site http://www.abb.com/abblibrary/DownloadCenter/,
where the wiring diagram is available 1SDM000091R0001.
A4
X
XV
X
XV
A1
A4
12
S33M/2
42
1
2XB2 3
XB2
1
36
36
36
38
38
35
35
38
35
*D)
Diagram 12
Information on the assembly is available on the web site http://www.abb.com/abblibrary/DownloadCenter/,
in particular with the kit sheet 1SDH000999R0609.

Table of Contents

Other manuals for ABB SACE Emax 2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB SACE Emax 2 and is the answer not in the manual?

ABB SACE Emax 2 Specifications

General IconGeneral
BrandABB
ModelSACE Emax 2
CategoryCircuit breakers
LanguageEnglish

Related product manuals