ABB | SACE Emax 2
Ekip Dip protection trip unit | 2 - Protections
43 | © 2017 ABB | 1SDH000999R0002 - ECN000058721 - Rev. B
Summary table of protections
ABB
ANSI
(5)
Threshold
(1)
Threshold
tolerance
(3)
Time
(1)
Calculation
formula t
t
(2)
Example
calculation t
t
(2)
Tolerance t
t
(3)
L 49
I1 =
0.4…1 In
activation for If in the
range (1.05...1.2)
x I1
t1 =
3…144 s
t
t
=
(9 t1) / (If / I1)
2
t
t
= 6.75 s with:
I1 = 0.4 In; t1 = 3 s;
If = 0.8 In
± 10 % with If 6 In
± 20 % with If > 6 In
S
(t = k)
50 TD
I2 =
0.6...10 In
± 7 % with If 6 In
± 10 % with If > 6 In
t2 =
0.1…0.8 s
t
t
= t2 -
The better of the two
values:
± 10 % or ± 40 ms
S
(t = k / l
2
)
51
I2 =
0.6...10 In
± 7 % with If 6 In
± 10 % with If > 6 In
t2 =
0.1…0.8 s
t
t
=
(100 t2) / (If)
2
t
t
= 5 s con:
I2 = 1 In; t2 = 0.8 s;
If = 4 In
± 15 % with If 6 In
± 20 % with If > 6 In
I 50
I3 =
1.5...15 In
± 10 % Not adjustable t
t
30 ms - -
G
(t = k)
50N TD
I4
(4)
=
0.1...1 In
± 7 %
t4 =
0.1…0.8 s
t
t
= t4 -
The better of the two
values:
± 10 % or ± 40 ms
G
(t = k / l
2
)
51N
I4
(4)
=
0.1...1 In
± 7 %
t4 =
0.1…0.8 s
t
t
=
2 / (If / I4)
2
t
t
= 0.32 s with:
I4 = 0.8 In; t4 = 0.2
s; If = 2 In
± 15 %
Iinst -
Defined by
ABB
- Instantaneous - - -
(1)
See the serigraph for the available combinations.
(2)
t
t
calculation is valid for If values that have exceeded the trip threshold of the protection. Use fault current and threshold values expressed in In to
calculate t
t
, as shown in the example.
(3)
Tolerances valid with trip unit energized in service conditions or with the auxiliary; tripping time 100 ms, temperature and currents within operating
limits. If the conditions are not guaranteed, the tolerances in the table shown below apply.
(4)
All thresholds are activated in the presence of auxiliary power supply. If there is no auxiliary power supply, the minimum threshold is automatically
limited to 0.2 In.
(5)
ANSI / IEEE C37-2 encoding.
Key
(t=k) - Fixed time curve
(t=k/I
2
) - Dynamic time curve
t
t
- Tripping time
If - Primary fault current
Tolerances in particular cases
If the conditions defined in point
(3)
of the above table are not guaranteed, the following tolerances apply:
Protection Tolerance threshold
Tolerance t
t
L Activation for If in the range (1.05...1.2) x I1 ± 20 %
S ± 10 % ± 20 %
I ± 15 % 60 ms
G ± 15 % ± 20 %

Table of Contents

Other manuals for ABB SACE Emax 2

Question and Answer IconNeed help?

Do you have a question about the ABB SACE Emax 2 and is the answer not in the manual?

ABB SACE Emax 2 Specifications

General IconGeneral
TypeAir circuit breaker
Rated Current800 A to 6300 A
Breaking CapacityUp to 150 kA at 415 V AC
Frequency50/60 Hz
Number of Poles3, 4
InstallationFixed or withdrawable
StandardsIEC 60947-2
Trip UnitEkip Touch, Ekip Hi-Touch
CommunicationModbus, Profibus, Ethernet
Rated Voltage690 V AC

Summary

Transport and Checking on Receipt

Description

Circuit-breaker Overview

Details of circuit-breaker types, structure, and components.

Environmental Conditions

Installation Environment

Requirements for dry, dust-free installation locations, and environmental factors.

Installation

Warnings and Precautions

Safety guidelines before starting installation procedures.

Ekip Protection Trip Units

Introduction and Trip Unit Overview

General introduction to Ekip trip units, types, and functions.

Ekip Dip Interface and Protections

Details of the Ekip Dip interface, operator controls, and protection functions.

Accessories

Putting into Service and Maintenance

Putting into Service

General checks and procedures for initial setup and commissioning.

Alarms and Failures

Identifying and resolving faults, causes, and error signals.

Maintenance Operations

Procedures for inspection, cleaning, lubrication, and testing.

Related product manuals