ABB | SACE Emax 2
82 | © 2017 ABB | 1SDH000999R0002 - ECN000058721 - Rev. B
Electrical accessories | 2 - Electrical signalling accessories
S51: trip unit tripping signalling
contact
98
96
95
S51
The S51 contact signals the opening of the circuit-breaker due to tripping of the Ekip protection trip unit.
It is available in two different types:
standard contact
contact for digital signals
NOTE: The standard S51 contact is always included in automatic circuit-breakers, and is
associated with the TU Reset mechanical signalling.
The following table provides information on the electrical characteristics:
Characteristics Standard Digital signals
Breaking
capacity
DC
24V - 0.1 A
125V
0.3A @ 0ms -
0.15A @ 10ms -
250V
0.3A @ 0ms -
0.15A @ 10ms -
AC 125V - 250V
1.5A cos φ 0.3 -
3A cos φ 0.7 -
5A cos φ 1 -
Minimum load 100mA @ 24V 1mA @ 5V
S51: Connections
Further information is available on page 59, or on the site http://www.abb.com/abblibrary/DownloadCenter/,
where the wiring diagram is available 1SDM000091R0001.
A4
X
XV
X
XV
A1
A4
96
95
95
95
98
98
98
96
96
XB7 1
3XB7 2
S51
11
Diagram 11
Information on the assembly is available on the web site http://www.abb.com/abblibrary/DownloadCenter/,
in particular with the kit sheet 1SDH000999R0605.

Table of Contents

Other manuals for ABB SACE Emax 2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB SACE Emax 2 and is the answer not in the manual?

ABB SACE Emax 2 Specifications

General IconGeneral
BrandABB
ModelSACE Emax 2
CategoryCircuit breakers
LanguageEnglish

Related product manuals