Calibrate Your Analog Modules 133
14. Repeat these steps to calibrate the other channel, if desired.
Both high and low inputs must be accepted in order for the module to
finish calibration.
Calibration is now complete. If the module does not accept calibration
(status indicator is still blinking), from the Device Parameters dialog, click
Abort Calibration and start over.
Calibrate the Analog
Voltage Output Module
To calibrate your output module, connect the module in a DeviceNet system
similar to that shown in the figure and use this procedure.
IMPORTANT
Apply power to the power supply and module for at least
10 minutes before calibrating the module. This allows
internal temperatures to stabilize, and reduces drift errors.
01 01 01 01
01
01
Power Supply Voltage
DeviceNet Input
250 Ω
Channel 0
Connect to 0 and 4
Channel 1
Connect to 1 and 5
PDN OE2V
Voltage Meter