150 Rockwell Automation Publication 520-UM001G-EN-E - September 2014
Chapter 4 Troubleshooting
Common Symptoms and
Corrective Actions
The drive is designed to start from the keypad when shipped. For a basic test of
drive operation:
1. Remove all user I/O wire.
2. Verify safety terminals (S1, S2 and S+) jumper is in place and tightened.
3. Verify wire jumper is in place between I/O terminals 01 and 11.
4. Verify that the three jumpers are in their proper default positions on the
control board. See PowerFlex 525 Control I/O Wiring Block Diagram
on
page 39 for more information.
5. Reset default parameter values by setting P053
[Reset Defalts] to 2
“Factory Rset”.
6. If safe to do so for your application, press Start on drive keypad. Drive will
run according to the speed potentiometer.
F122 I/O Board Fail 2 Failure has been detected in the drive
control and I/O section.
Cycle power.
Replace drive or control module if
fault cannot be cleared.
F125 Flash Update Req 2 The firmware in the drive is corrupt,
mismatched, or incompatible with the
hardware.
Perform a firmware flash update
operation to attempt to load a valid set
of firmware.
F126 NonRecoverablErr 2 A non-recoverable firmware or
hardware error was detected. The drive
was automatically stopped and reset.
Clear fault or cycle power to the
drive.
Replace drive or control module if
fault cannot be cleared.
F127 DSIFlashUpdatReq 2 A critical problem with the firmware
was detected and the drive is running
using backup firmware that only
supports DSI communications.
Perform a firmware flash update
operation using DSI communications to
attempt to load a valid set of firmware.
(1) This fault is not applicable to PowerFlex 523 drives.
(2) See Fault Types
for more information.
(3) This fault may be cleared by the auto-restart routine and will be attempted only once. It ignores the value set in parameter A541
[Auto Rstrt Tries].
Fault Types, Descriptions and Actions
No. Fault Type
(2)
Description Action

Table of Contents

Other manuals for Allen-Bradley PowerFlex 525

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley PowerFlex 525 and is the answer not in the manual?

Allen-Bradley PowerFlex 525 Specifications

General IconGeneral
BrandAllen-Bradley
ModelPowerFlex 525
CategoryController
LanguageEnglish

Related product manuals