24 Rockwell Automation Publication 6000-IN006F-EN-P - March 2018
Chapter 2 Drive Electrical Installation
Electrical Drawings
Before connecting any power cables or control signal wiring, review and
understand the information contained in the project-specific Electrical
Drawings.
They contain critical information such as:
Minimum power cable insulation ratings and sizes
Power terminal locations and designations
Terminal block designations for all connections to external customer
control signal wiring and control power supply cables.
The practice used within the PowerFlex 6000 electrical drawing is based on the
IEC or NEMA standard depending on the requirements. The symbols used to
identify components on the drawings are international.
Device designations used on the drawings and labeling are explained on each
drawing set.
Wiring identification uses a source/destination wire number convention on
point-to-point multi-conductor wiring and in situations where the system is
warranted. The wire-numbering system of unique, single numbers for multi-drop
and point-to-point wiring continues to be used for general control and power
wiring.
Wiring that connects between the sheets or that ends at one point and starts at
another point on a drawing has an arrow and drawing reference to indicate the
ongoing connection. The drawing reference indicates the sheet and the X/Y
coordinates of the continuation point. The reference system is explained on a
sheet in each drawing set. The unique wire numbering system serves as
confirmation that the correct wire is being traced from sheet-to-sheet or across a
drawing. Wires in multi-conductor cables are typically identified by color rather
than by number. Abbreviations used to identify the colors on the drawings are
fully identified on a sheet in the drawing set.
Grounding System
Requirements
As a general guideline, the ground path must be of sufficiently low impedance
and capacity that:
the rise in potential of the drive ground point when subjected to a current
of twice the rating of the supply should be no higher than 4 V over ground
potential
the current flowing into a ground fault is of sufficient magnitude to cause
the protection to operate.
The general grounding point must be reliably connected with the grounding
network.

Table of Contents

Other manuals for Allen-Bradley PowerFlex 6000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley PowerFlex 6000 and is the answer not in the manual?

Allen-Bradley PowerFlex 6000 Specifications

General IconGeneral
BrandAllen-Bradley
ModelPowerFlex 6000
CategoryDC Drives
LanguageEnglish

Related product manuals