74 Rockwell Automation Publication 750-QS001A-EN-P - March 2015
Reference Section
Analog Output Wiring
Table 50 - 753 Main Control Board TB1 Analog Output Wiring
Analog Voltage Output
±10V, 0…20 mA Bipolar
+10V Unipolar
753 Main Control Board TB1
Configuration
Port 0: P270 [Anlg Out Type], bit 0 = 0
Set Selection
Port 0: P275 [Anlg Out0 Sel] = Port 0: P3 [Mtr Vel Fdbk]
Adjusting Scale
Port 0: P278 [Anlg Out0 DataHi] = 60 Hz
Port 0: P279 [Anlg Out0 DataLo] = 0 Hz
Port 0: P280 [Anlg Out0 Hi] = 10V/20 mA
Port 0: P281 [Anlg Out0 Lo] = 0V/0 mA
View Results
Port 0: P277 [Anlg Out0 Data]
Port 0: P282 [Anlg Out0 Val]
Table 51 - 750-Series I/O Module TB1 Analog Output Wiring
Analog Voltage Output
±10V, 0…20 mA Bipolar
+10V Unipolar
750-Series I/O Module TB1
Configuration
Port 4 (or port where your I/O module is installed): P70 [Anlg Out Type], bit 0 = 0
Set Selection
Port 4 (or port where your I/O module is installed): P75 [Anlg Out0 Sel] = Port 0: P3 [Mtr Vel Fdbk]
Adjusting Scale
Port 4 (or port where your I/O module is installed): P78 [Anlg Out0 DataHi] = 60 Hz
Port 4 (or port where your I/O module is installed): P79 [Anlg Out0 DataLo] = 0 Hz
Port 4 (or port where your I/O module is installed): P80 [Anlg Out0 Hi] = 10V/20 mA
Port 4 (or port where your I/O module is installed): P81 [Anlg Out0 Lo] = 0V/0 mA
View Results
Port 4 (or port where your I/O module is installed): P77 [Anlg Out0 Data]
Port 4 (or port where your I/O module is installed): P82 [Anlg Out0 Val]