3-26 Programming and Parameters
PowerFlex 40 Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual
Publication 22B-UM001I-EN-E
Advanced Program Group (continued)
A084 [Boost Select] Related Parameter(s): d004, P031, P032, A085,
A086
, A087, A125
Sets the boost voltage (% of P031 [Motor NP Volts]) and redefines the Volts per Hz curve.
Active when A125 [Torque Perf Mode] = 0 “V/Hz”.
Drive may add additional voltage unless Option 5 is selected.
Options 0 “Custom V/Hz”
1 “30.0, VT”
Variable Torque (Typical fan/pump curves.)
2 “35.0, VT”
3 “40.0, VT”
4 “45.0, VT”
5 “0.0 no IR”
Constant Torque
6 “0.0”
7 “2.5, CT”
[Default for
4.0, 5.5, 7.5 & 11 kW
(5.0, 7.5, 10 & 15 HP)
Drives]
8 “5.0, CT” (Default)
9 “7.5, CT”
10 “10.0, CT”
11 “12.5, CT”
12 “15.0, CT”
13 “17.5, CT”
14 “20.0, CT”
% P032 [Motor NP Hertz]
% P031 [Motor NP Volts]
100
50
1/2 [Motor NP Volts]
1/2
[Motor NP Hertz]
4
3
2
1
050100
Settings
5-14
22B-UM001.book Page 26 Tuesday, May 30, 2017 5:22 PM
Aotewell Ltd
www.aotewell.com
Industry Automation
HongKong|UK|China
sales@aotewell.com
+86-755-8660-6182

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley PowerFlex40 and is the answer not in the manual?

Allen-Bradley PowerFlex40 Specifications

General IconGeneral
BrandAllen-Bradley
ModelPowerFlex40
CategoryController
LanguageEnglish

Related product manuals