5.2 Calibration of positioner board (OPTION)
!
Make sure that the board is connected to the power supply
during the calibration process.
This operation must be carried out by a qualified
electrician.
The proportional analog
command allows you to
drive the valve to
intermediate positions.
The board is factory pre-
set.
Perform the electrical
wiring according to the
wiring diagram of the
actuator.
5.2.1 Setting up positioner board
The actuator is delivered with the proportional analog
command already installed, and calibration has already
been performed at our factory.
Only go through the setup procedure below if you previously had to
adjust the mechanical end stops positions.