SG-150-1 13
5. Control of the CM-SW-01
Control commands and setpoint can be given to the CM-SW-01 via different interfaces
Digital inputs: Start/stop
Analogue input: Setpoint
Serial control: Commands and setpoint
The commands from the different interfaces are merged and the resulting “Control Word” can be read via
the serial Interface.
The capacity is limited between 10 % and 100 % even if the sum of the setpoints may be below 10 % or
above 100 %.
The serial protocol is Modbus (RTU). Modbus can be connected for example for monitoring only but still
using the digital and analogue inputs for control of the CM-SW-01. Most common is to monitor and control
the CM-SW-01 via the Modbus interface.
The serial control is inactive by default. Please see section 5.2 Enable serial control.
5.1 Commands and setpoint
The basic operation of the CM-SW-01 is controlled by
Commands: Start and stop
Setpoint analogue or serial control
Setting of serial control parameters
o "Serial Control Source"; default is none: 0 10V input
See parameter in section 10.5.1 Configuration application
o Setting of the refrigerant (if not done via the BEST Software)
Commands and setpoint can be given via the digital and analogue inputs or by combining the digital and
analogue inputs with values from the serial interface. See later in this section.
5.1.1 Command Start
The Start command becomes active when a start signal is given via digital input or serial control.
If the compressor is started too many times per hour, the CM-SW-01 will give a waning but the compressor
will be allowed to start
The capacity of the compressor will normally match the setpoint. Details are described below.
When the motor is running and the start condition is removed (Start is set to inactive), the compressor is
stopped.
5.1.2 Setpoint and speed changes
The setpoint is a value in the range -100 % to +100 %. There is no ramping of a capacity change request.
The setpoint from the analogue input and the serial control are added. E.g. the analogue signal could be an
offset and the serial control could be the fine tuning.
Analogue control: Apply a 0 10V capacity signal (0 100%) to the CN13 Cap. Input.
Serial control: Set the capacity request in parameter Serial Setpoint (-100 % +100%)
Please see section 10.3.1 Control application for the parameter to use for the setpoint.
5.2 Enable serial control
The serial control is inactive by default.
To enable the serial control set the parameter to 1 (COM1 Modbus).
To disable serial control:
Set parameter “Serial Control Source” to 0 (= None).

Table of Contents

Other manuals for Bitzer CM-SW-01

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bitzer CM-SW-01 and is the answer not in the manual?

Bitzer CM-SW-01 Specifications

General IconGeneral
BrandBitzer
ModelCM-SW-01
CategoryControl Unit
LanguageEnglish

Related product manuals