SG-150-1 37
Name
Possible
values
Default
Description
Modbus
type & addr
COM1 Stop Bits
1 - 2
scale 1
uint8
1
Number of stop bits
(1=1 Stopbit, 2=2 Stopbits)
HR 65411
COM1 Parity
0 - 2
scale 1
uint8
1
Parity check
(0=None, 1=Even, 2=Odd)
HR 65412
Setting of the parameters Address, Baud rate and Parity via BEST Software or Modbus will not result in
immediate changes of the communication. The setting will be made active by cycling power to the module.
10.5.4 Logs application
The group contains runtime counters for the application
Name
Possible
values
Default
Description
Modbus
type & addr
Device Operating
Hours
unit h
scale 1
uint32
-
Device Operating Hours
IR 30000-
30001
Compressor Running
Hours
unit h
scale 1
uint32
-
Compressor Running Hours
IR 30010-
30011
Compressor Start
Count
unit None
scale 1
uint32
-
Compressor Start Count
IR 30012-
30013
Power Up Count
unit None
scale 1
uint32
-
Number of module power cycles
IR 30020-
30021
10.5.5 Info compressor type
The group lists the compressor type
Name
Possible
values
Default
Description
Modbus
type & addr
Compressor type
selection
unit None
scale 1
uint16
3067
Compressor type selection
(0=NONE, 3067=OSKA95103-K)
IR 42100

Table of Contents

Other manuals for Bitzer CM-SW-01

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bitzer CM-SW-01 and is the answer not in the manual?

Bitzer CM-SW-01 Specifications

General IconGeneral
BrandBitzer
ModelCM-SW-01
CategoryControl Unit
LanguageEnglish

Related product manuals