16 SG-150-1
5.7 Setting the serial setpoint
The serial setpoint is set via the Modbus holding register 111:
Name
Possible
values
Default
Description
Modbus
type & addr
Serial Setpoint
(Control.SerSetpoint)
-100.00 % -
100.00 %
scale 100
sint16
0 %
Capacity setpoint written by serial
communication
HR 111
5.8 Serial Control Timeout Function
If the communication is interrupted, the CM-SW-01 can be configured for different reactions to this interrupt
None continue operation
Stop stop operation
Fault Stop and signal fault alarm
Default function is to let the CM-SW-01 continue without any changes (None).
The timeout for activation and the different reactions of the Serial Control Timeout Function can be adjusted.
Every update of the Serial control word resets the timeout function.
Default timeout is 60 seconds.
Please see section 10.5.1 Configuration application for further information.