10.2 OTHER HUMIDITY FUNCTIONS
The high and low humidity alarms cause alarm screen signalling and have modifiable delay time.
10.3 CLOSE CONTROL UNITS WITH WATER COILS
In these close control units, the cold water coils provide for dehumidification. The humidification devices are the same as the direct expansion
close control units ones (On-Off contact, 0-10Volt modulating signal, built-in humidifier): for any information about their operation, refer to the
previous paragraph. The following diagrams show the dehumidification devices action. The percentage values indicate the modulating valves
opening range. Please note that the dehumidification cold water coils are enabled at 100%, not in modulating mode, in case of both three-
position and 0-10Volt valves.
Ambient
humidit
%
HUMIDIFICATION
100%
100%
Dehumidification proportional band
Humidification proportional band
Humidity set
VALVOLA AC
UA FREDDA 0-10V
48.0 50.0 52.0
2.0% 2.0%
50.0 52.0
50.0 52.0
VALVOLA AC
UA FREDDA 3 PUNTI
100%
0%
Ambient
humidit
%
Ambient
humidit
%
100%
0%
-
-
DEHUMID.
HUMIDIF.
Humidity set
Humid. band Dehum. band
Low humidit
alarm Hi
h humidit
alarm
2.0% 2.0%
10.0% 10.0%
Ambient
humidit
%