IGS-NT Communication Guide
37
Controllers
Controllers IG-NT-BB IM-NT-BB IG-NTC-BB IS-NTC-BB IM-NTC-BB
Connection
applicable
YES YES YES YES YES
Available
ports
RS232(1) RS232(1) RS232(1) RS232(1) RS232(1)
More info
IG/IM-NT-BB - Communication
(page 16)
IG/IS/IM-NTC-BB - Communications (page 12)
Controllers IG-NT-BB IG-NTC IS-NT-BB IM-NT
Connection
applicable
YES YES YES YES
Available
ports
RS232(1)
RS232(1)
RS232(2)
RS232(1)
RS232(2)
RS232(1)
More info
IG-NT -
Communications,
Terminals (page 20)
IG-NTC -
Communication,
Terminals (page
21)
IS-NT-BB -
Communications,
Terminals (page 23)
IM-NT -
Communications,
Terminals (page 22)
Note: Other way how to realize RS232 connection is via RS232/RS485 – MODBUS (I-LB+) (page 42).
Controller setup
(Setpoints/Comms settings group)
RS232(1 or 2) mode = MODBUS-DIRECT
RS485(1 or 2) conv. = DISABLED
RS232(1)MBCSpd = 9600, 19200, 38400, 57600
Equipment
Equipment needed
Controller side -
Connection RS232 cable (page 83) cable up to 10 m
Other device
side
RS232 connection or RS232/USB converter