7.2.6 Gen-set control
SMS command for invoking gen-set control command as Start, Stop, Fault reset etc.
Syntax:
c Y (or cY)
c command
Y type of operation
Y Type of operation Y Type of operation
1 Start 7 MCB ON
2 Stop 8 MCB OFF
3 Horn Reset 9 GCB ON/OFF
4 Fault Reset 10 MCB ON/OFF
5 GCB ON 11 Next Mode
6 GCB OFF 12 Previous Mode
Example:
#5:accesscode p 1234, c1
This SMS command invokes gen-set Start. Password setting is needed in case of
password protection was configured for gen-set commands.
Returncode:
ok gen-set command was accepted
er_pass valid password was not set before executing the command
c? unknown gen-set command
c_er gen-set command execution is not allowed in actual state (e.g. attempt to start the
gen-set in OFF mode).
er_old command was read out from SMS during GSM modem initialization in this case
command will not be served.
7.2.7 Read Alarm list
Read actual Alarm list.
Syntax:
a
a command
Example:
#5:accesscode a
Request of actual Alarm list.
Returncode:
AL=(items of alarm list) comma separated items of Alarm list. Exclamation mark in front
of Alarm list item indicates inverse record (still active alarm).
Note:
1. Answer message contains at most eight items of Alarm list.
2. Alarm list is not separated to more messages.

Table of Contents

Other manuals for ComAp InteliGen NT

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliGen NT and is the answer not in the manual?

ComAp InteliGen NT Specifications

General IconGeneral
BrandComAp
ModelInteliGen NT
CategoryController
LanguageEnglish

Related product manuals