IGS-NT Communication Guide
75
5.7 Commands for IM-NT
First it is necessary to enter an appropriate user and his password to enable commands, if these are protected
by level 1-7.
Command Meaning Argument(*) Return Value(*)
1
Start command 01FE0000
000001FF OK
2
Argument has not
been written
Stop command 02FD0000
000002FE OK
2
Argument has not
been written
Horn reset 04FB0000 000004FC OK
Fault reset 08F70000 000008F8 OK
other 1 Wrong argument
2
Close/open MGCB 11EE0000
000011EF OK
2
Argument has not
been written
Close MGCB 11EF0000
000011F0 OK
2
Argument has not
been written
Open MGCB 11F00000
000011F1 OK
2
Argument has not
been written
Close/open MCB / BTB 12ED0000
000012EE OK
2
Argument has not
been written
Close MCB / BTB 12EE0000
000012EF OK
2
Argument has not
been written
Open MCB / BTB 12EF0000
000012F0 OK
2
Argument has not
been written
other 1 Wrong argument
5 Reset from Init state (#1) 44440000
00004445 OK
1
Not possible to
perform
8 Set kWh counter New value N/A
C Set kVAhr counter New value N/A
001A
Set binary output RemoteSwitch1-8
(RemoteControl1-8)
00200000x(**) N/A
Reset binary output RemoteSwitch1-
00100000x(**) N/A