Command
(*)
Meaning Argument(*) Return Value(*)
1
Start the engine – in one
step (page 106)
01FE0000
000001FF OK
2
Argument has
not been
written
Engine stop 02FD0000
000002FE OK
2
Argument has
not been
written
Horn reset 04FB0000 000004FC OK
Fault reset 08F70000 000008F8 OK
ECU Fault reset 10EF0000 000010F0 OK
other 1
Wrong
argument
2
Close/open generator circuit
breaker (IGS-NT)
Clutch ON/OFF (ID)
11EE0000
000011EF OK
2
Argument has
not been
written
Close generator circuit breaker 11EF0000
000011F0 OK
2
Argument has
not been
written
Open generator circuit breaker 11F00000
000011F1 OK
2
Argument has
not been
written
Close/open mains circuit
breaker
12ED0000
000012EE OK
2
Argument has
not been
written
Close mains circuit breaker 12EE0000
000012EF OK
2
Argument has
not been
written
Open mains circuit breaker 12EF0000
000012F0 OK
2
Argument has
not been
written
other 1
Wrong
argument