InteliLite Global Guide
100
shutdown alarm in the alarmlist. Activates the output AL COMMON SD (PAGE 544) as well as the standard alarm
outputs (HORN (PAGE 581) and ALARM (PAGE 552)).
Breaker open and cool down (BOC)
The event appears in the alarmlist and is recorded into the history log. It causes immediate opening of the GCB
and then the standard stop sequence with cooling follows. The gen-set cannot be started again while there is a
BOC alarm in the alarmlist. Activates the output AL COMMON BOC (PAGE 544) as well as the standard alarm
outputs (HORN (PAGE 581) and ALARM (PAGE 552)).
Sensor fail detection (FLS)
If the measured resistance on an analog input exceeds the valid range, a sensor fail will be detected and a
sensor fail message will appear in the Alarmlist (page 101). The valid range is defined by the most-left (RL)
and most-right (RH) points of the sensor characteristic ±12.5% from RH-RL.
Note: Sometimes there can be problem with lower limit of valid range which can be counted as negative
number. In this case the lower limit is set as one half of the RL point of the sensor curve characteristic.
Image 5.17 Sensor fail detection principle
Remote alarm messaging
If communication plug-in module is connected to the controller, the controller can send SMS messages and
emails at the moment when a new alarm appears in the Alarmlist (page 101) or new event is written in History
log (page 103). The message will contain a copy of the Alarmlist (page 101) or reasons from History log
(page 103). To enable this function, adjust setpoints Event Message (page 374), Wrn Message (page 375),
BOC Message (page 375) and Sd Messages (page 375) to ON. Also enter a valid GSM phone number or
email address to the setpoints Telephone Number 1 (page 368), Telephone Number 2 (page 368),
Telephone Number 3 (page 369), Telephone Number 4 (page 369), Email Address 1 (page 371) Email
Address 2 (page 372)Email Address 3 (page 372), and Email Address 4 (page 373).
The list of all supported terminals shows the table below:

Table of Contents

Other manuals for ComAp InteliLite MRS16

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite MRS16 and is the answer not in the manual?

ComAp InteliLite MRS16 Specifications

General IconGeneral
BrandComAp
ModelInteliLite MRS16
CategoryController
LanguageEnglish

Related product manuals