5.5.1 Start-stop sequence
State Condition of the transition Action Next state
Ready Start request PRESTART (PAGE 585) on Prestart
Time (page 191) counter started
Prestart
RPM > 2 or Oil pressure > Starting
Oil Pressure (page 192) or
Generator voltage > 10V or D+
voltage is higher than D+ Treshold
(page 206)
Stop (Stop
fail)
OFF Mode selected or Shutdown
alarm active
Not Ready
Not Ready RPM < 2, Oil pressure not detected,
Generator voltage < 10V, D+ not
Ready