InteliLite Global Guide
16
2.5.5 EM-BIO8-EFCP
Hybrid current input and binary input/output extension module.
One additional AC current (CT) measuring for
Earth Fault Current protection (EFCP)
Wide range of measured current - one input for
1A and 1 input for 5A
Up to 8 additional configurable binary inputs or
outputs
2.6 CAN modules
2.6.1 Inteli IO8/8
The unit offers the user the flexibility to configure the unit to have 8 binary inputs, 8 binary outputs, and 2 analog
outputs, or 16 binary inputs, 0 binary outputs and 2 analog outputs via switches inside the controller.
Configuration 8/8
8 Binary inputs (options: pull up or pull down
logic)
8 Binary outputs (options: Low side switch (LSS)
or High side switch (HSS))
2 Analog outputs (options: voltage (0-10V),
current (0-20mA) and PWM (5V, adjustable
frequency 200Hz-2,4kHz))
Configuration 16/0
16 Binary inputs (options: pull up or pull down
logic)
0 Binary outputs
2 Analog outputs (options: voltage (0-10V),
current (0-20mA) and PWM (5V, adjustable
frequency 200Hz-2,4kHz))