InteliLite Global Guide
688
Alarm Type BOC
Alarmlist message BOC Overload
Alarm evaluated All the time
Related applications AMF, MRS
Description
The alarm is issued when the gen-set power is over the limit for time period longer
than the delay. The behavior of the overload alarm is adjusted by the following
setpoints:
Overload BOC (page 227) adjusts the overload limit.
Overload Delay (page 227) adjusts the delay
BOC Overload
6 back to List of alarms level 2
Alarm Type Shutdown
Alarmlist message BOC Rental Timer
Alarm evaluated All the time
Related applications AMF, MRS
Description This alarm occurs when Rental Timer BOC (page 321) elapses.
BOCRental Timer
6 back to List of alarms level 2
Alarm Type BOC
Alarmlist message BOC Short Circuit
Alarm evaluated All the time
Related applications AMF, MRS
Description
This is a fast overcurrent protection. The following setpoints are related to this
alarm:
Short Circuit BOC (page 228) adjusts the short current limit
Short Circuit BOC Delay (page 228) adjusts the delay in fine steps
BOC Short Circuit
6 back to List of alarms level 2
Alarm Type Alarm indication + history record
Alarmlist message ECU Red Lamp
Alarm evaluated All the time
Related applications AMF, MRS
Description
This alarm is activated when ECU send information that ECU Red lamp is
activated. LBO ALARM (PAGE 552)is not activated, after deactivation of lamp,
alarm automatically disappear.
Note: This alarm doesn't stop the engine.
ECU Red Lamp
6 back to List of alarms level 2