The b configuration code (b) is a secondary configuration code that
changes display options and the forecourt communication operation.
1. Make sure that the dispenser is idle, with the nozzle in its holster
2. Press and release the K-Factor switch until b is displayed.
3. Enter the new b configuration.
Each press of the K-Factor switch passes you over a digit
in a setting, making the digit blink. Holding the switch down for more than
a second changes whichever digit is currently displayed. If you want to
pass over a setting without changing any digits, keep pressing and
releasing the switch.
4. Let the menu time out so that the value and quantity amounts are
displayed.
In stand-alone operation/monitor mode [b 0XXX], the dispenser
operates even when not connected to a site Controller. If it is connected to a
controller, it will only dispense gas when authorised by the controller. If the
controller is turned off and the dispenser power is cycled off and on, the
dispenser will operate in standalone mode.
In Controller mode [b 1XXX], the dispenser only operates if it is connected to
a site Controller. Transactions are displayed.
Flow mode [b XX2X] is used to view the current flow rate of the
gas. When this mode is set FLO will appear in the value display and the
current flow rate value will appear in the unit price display. This is used for
testing only and not during normal dispenser operation.