Scheduled Servicing
Weekly checks
Check the sealing and operation of the three-way refuelling valve (see page 46).
Check the sealing and operation of the solenoids. Refer to: Checking the Sealing of the Solenoid (see page 42)
Check the sealing and setting of the regulator. (see page 43)
Drain the Coalescing Filter (see page 46).
Suggested 6-monthly or 4000 compressor run hour service
Check the dispenser for leaks (see page 45).
Check the Coalescing filter elements, replace if necessary. (see page 47)
Check damage and electrical continuity of Refuelling Hoses
Replace Breakaway seals
Replace 3-way refuelling valve seals and inspect ball for scratches and wear. Replace ball if necessary. (see page
55)
Replace refuelling probe O-rings. Check that the probe is not damaged or bent, replace if necessary
OEM Nozzles and Breakaways - Refer to manufacturer’s instructions
Suggested yearly or 8000 compressor run hour service
In addition to all the checks listed in the 6-month service, carry out the following:
Dismantle and clean the solenoid valves. Replace the seals and O-rings (see page 48).
Dismantle and clean the regulator valves. Replace the seals and O-rings (see page 52).
Check the dispenser calibration. Meter Calibration (see page 67).
Check the C4000 Processor Board is clean, dry and dust free.
Check the UPS and voltage stabiliser supplying power to the dispenser is working according to the manufacturer’s
specifications.
Check the C4000 flameproof box lid is bolted down tight and all glands are tight.
Check the zero point and calibration of the dispenser pressure transducers (fast fill & temperature compensation
only).