Test Operation SiUS181631EA
118 Test Operation and Field Settings
1.3 Branch Provider (BP) Unit
1.3.1 Judging and reprogramming in case of redundant BP addresses
The BP unit of this system is provided with specific addresses in its production stage. These
addresses are for various controls. If by any chance (on 3 out of 260000 units) these addresses are
redundant, the system may get in trouble. When replacing the PCB of the BP unit too, these
addresses may be used repeatedly.
Address redundancy checking flowchart
Reprogramming the PCB addresses of BP unit
Modify the DIP switch (DS2) settings on the BP unit's PCB in the following way.
With the system set up, power on both the
outdoor unit and BP unit.
The compressor is in a non-startup
condition.
Example: thermostat control off,
alarm being issued, heating with
high outdoor
air temperature, compressor
failure, etc.
BP addresses redundancy.
Reprogram the addresses.
Normal
Set the outdoor unit PCB in the monitor mode
and check the number of indoor units being
connected.
Is the number of connected indoor units correct?
Give a start command from the indoor unit. Does
the compressor start in 20 minutes? (Test
operation cannot be made either.)
No
No
Ye s
Ye s
(Q0517)
(R19088)
H1P (LED A)
H2P (LED 1)
H3P (LED 2)
H4P (LED 3)
H5P (LED 4)
OFF ON
DS2-1
DS2-2
DS2-3
DS2-4
DS2