Page #146 background image
Field Settings SiUS181631EA
136 Test Operation and Field Settings
Detailed Setting Procedure of Low Noise Operation and Demand Control
1. Setting mode 1 (H1P off)
In setting mode 2, press BS1 (MODE button) one time.
→
The system enters setting mode 1
and the H1P goes off.
In setting mode 1, the H6P (In low noise operation) and the H7P (In demand control) keep
lighting.
2. Setting mode 2 (H1P on)
(1) In setting mode 1, press and hold BS1 (MODE button) for more than 5 seconds.
→
The system
enters setting mode 2 and the H1P lights up.
(2) Press BS2 (SET button) several times and match the LED display with the Setting No. you
want.
(3) Press BS3 (RETURN button) one time, and the present setting content is displayed.
→
Press BS2 (SET button) several times and match the LED display with the setting content
(as shown on next page) you want.
(4) Press BS3 (RETURN button) two times.
→
The system returns to (1).
(5) Press BS1 (MODE button) one time.
→
The system returns to setting mode 1 and the H1P goes
off.
{
: ON
z
: OFF
l
: Blink
(1) (2) (3)
Setting
No.
Setting
contents
Setting No. indication Setting No. indication Setting
contents
Setting contents indication (Initial setting)
H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P
12 External low
noise
setting/
Demand
setting
{zzzzzz{z z { { z z
NO (Factory
setting)
{zzzzz
l
YES
{zzzz
l
z
22 Night-time
low noise
setting
{ z { z { { z
OFF
(Factory
setting)
{zzzzz z
Level 1
{zzzzz
l
Level 2
{zzzz
l
z
Level 3
{zzzz
l l
26 Night-time
low noise
operation
start setting
{ z { { z { z
PM 8:00
{zzzz z
l
PM 10:00
(Factory
setting)
{zzzz
l
z
PM 0:00
{zzz
l
z z
27 Night-time
low noise
operation
end setting
{ z { { z { {
AM 6:00
{zzzz z
l
AM 7:00
{zzzz
l
z
AM 8:00
(Factory
setting)
{zzz
l
z z
29 Capacity
precedence
setting
{ z { { { z {
Low noise
precedence
(Factory
setting)
{zzzzz
l
Capacity
precedence
{zzzz
l
z
30 Demand
setting 1
{ z { { { { z
60 % of
rated power
consumption
{zzzz z
l
70 % of
rated power
consumption
(Factory
setting)
{zzzz
l
z
80 % of
rated power
consumption
{zzz
l
z z
32 Constant
demand
setting
{ { z z z z z
OFF
(Factory
setting)
{zzzzz
l
ON
{zzzz
l
z
Setting mode indication section Setting No. indication section Set contents indication section