EasyManuals Logo
Home>Danfoss>Controller>EKE 1A

Danfoss EKE 1A User Manual

Danfoss EKE 1A
84 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #79 background imageLoading...
Page #79 background image
ID
Symptom
Possible cause/Reaction
Solution
16
Flash gas
Loud refrigerant or undercharged refrigerant.
Charge the system with appropriate refrigerant capaci-
ty.
Check for leakage is the system.
If the valve is placed much higher than condenser
tweet check pressure dierence.
Flash gas can lead to high SH or low suction pressure
Use the right valve size.
Also refer to section “High Superheat” and “Suction
pressure too low”
Pressure drops across lter.
Check and replace the Stet.
17
Steppe valves open/ close
too slow
Incorrect selection of valve type.
Dane the correct valve type.
Incorrect valve installation.
Check the physical vale and cable and intake in light
way.
MOPD is higher than valve specication.
Check the valve spec and choose the correct vane.
Check valve speed setting.
Drive the stepper valve with the recommended Speed.
Too high or too low speed could result in loss step in
the valve.
For the user dened valves, check the other valve set-
tings such as current, duty cycle, holding current and
other relevant parameter.
18
Opening degree of valve at
maximum OD for longer
time period
Lack of cooling capacity.
Check the cooling capacity in the system Also check
section, expansion valve too small
The condenser pressure is too low.
Check the ambient temperature.
Adjust the condenser controller.
The lter drier is blocked by dirt
Replacement Filter drier.
Flash gas in liquid line due to loss of refrigerant or under-
charge of refrigerant.
Check section ash gas.
Wrong valve setting.
Check valor setting matching installed valve.
Pressure transmitter is wrongly dened.
Oita pressure range and correct pressure transmitter
type.
Wrong refrigerant selected
Choose the correct refrigerant in the controller.
19
Hunting or uctuation valve
position
Too high gain (Kp and KpTe) or too low integration time
(Tn).
Decrease Kp by factor of 1.5%
Increase Tn 25% of the set value.
Perform 1 and 2 in loop if needed.
S2 thermal contact.
Check mounting of S2 sensor, Check the installation
guide section temperature sensor mounting.
Fluctuating Al signal for SH reference.
Check Al signal quality.
Fluctuating pressure signal.
Check section Fluctuating pressure signal.
Fluctuating Superheat.
Check section Fluctuating Superheat.
20
Unstable OD on driving the
valve in Valve driver mode
Fluctuating Al signal.
Check the Al signal quality.
Use the Valve neutral zone feature.
21
Internal Leakage in the valve
Wrong selection of the valve.
Check the valve type and its setting.
Step loss in stepper motor valve.
Power cycle the controller.
Enable the step loss feature i.e. overdriving. choose the
recommended overdrive value with respect to the in-
stalled valve.
Drive the stepper valve with the recommended speed.
Too high or too low speed could result in loss step in
the valve.
Longer cables mounted than specied for the control-
ler.
Separate Valve cable from other high-power cables and
do not bundle the cables.
Blockage in the valve or high friction in the valve.
MOM, exceeded than specied in the valve specica-
tion.
© Danfoss | Climate Solutions | 2022.06 BC398828796060en-000101 | 79
Superheat controller, Type EKE 1A, 1B, 1C, 1D

Other manuals for Danfoss EKE 1A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss EKE 1A and is the answer not in the manual?

Danfoss EKE 1A Specifications

General IconGeneral
BrandDanfoss
ModelEKE 1A
CategoryController
LanguageEnglish

Related product manuals