36
Light Blocking delay / Lbd
If the cooler is placed where the ambient light is unstable, the ambient light sensor
can cause the cooler to toggle between ECO and normal mode.
The light blocking delay disables the light-sensor for a given time after ambient
light change from bright to dark, so that the cooler stays in ECO mode for at least
this time. When the cooler is in serving or pull-down mode, the light sensor is
de-activated and a change to ECO mode will be determined by the door-sensor.
0: No blocking of the ambient light sensor.
Eco Temperature Offset / Eto
This parameter gives a relative temperature in degrees. It is the difference in
temperature for Eco mode operation compared to Normal mode.
NOTE: Setting a temperature offset may be illegal in
some jurisdictions.
Pull down (sometimes known as Super Cool) is
a procedure for improving cooling performance,
accelerating the time used to reach the desired
temperature. Pull Down settings overrule all
other settings.
7.7 Pull Down / Pud
Danfoss ERC 102
ERC Front and Button Functionallity:
Danfoss ERC 102
Hold 3 sec: Menu
1 Click: Variable direct function, e.g.ECO/Night mode
1 Click: Variable direct function, e.g. light
Sub function: Up
1 Click: Temperature setpoint
Sub function: Down
Sub function: Back
Sub function: OK
ERC Front and Button Functionallity:
1 Click: Temperature setpoint
Danfoss ERC 102
Hold 3 sec: Menu
1 Click: Variable direct function, e.g.ECO/Night mode
1 Click: Variable direct function, e.g. light
Sub function: Up
1 Click: Temperature setpoint
Sub function: Down
Sub function: Back
Sub function: OK
ERC Front and Button Functionallity:
1 Click: Temperature setpoint
ERC menu
code
Default Min Max Unit
Conv
Unit Scale Default Access
Shop Ser OEM
Pull Down Pud
Pull-down Initiate
Temperature
Pit 50.0/122.0 -40.0/-40.0 50.0/122.0 C/F a °C/°F .1 -- -- RW
Pull-down Cycling PCy 30 0 360 no min 1 -- -- RW
Pull-down defrost Interval Pdi 15 0 48 no hour 1 -- -- RW
Pull-down duration Pdd 24 0 48 no hour 1 -- -- RW
Pull-down limit temp PLt 0.0/32.0 -55.0/-67.0 55.0/131.0 C/F a °C/°F .1 -- -- RW
Pull-down reduction
temp △t
Prt 0.1/0.2 0,0 10.0/16.0 C/F r K/°R .1 -- -- RW
ERC
102 Reference manual – 7 PARAMETERS