42
Display Intensity / din
ERC 102 can have its display intensity (brightness) set in one of two ways:
A) with a Danfoss ambient light sensor attached, the brightness of the display is
adjusted automatically according to the ambient light level (see the Assignments
section)
B) when no ambient light sensor is attached, the display intensity can be set to
a fixed intensity.
Both options are on a scale of 1 to 10, where 10 is the brightest.
7.11 Assignments / ASi
ERC menu
code
Default Min Max Unit
Conv
Unit Scale Default Access
Shop Ser OEM
Assignments ASi
S1 Config S1C Stn Stn dig no -- -- RW
S2 Config S2C Stn Stn dig no -- -- RW
S3 Config S3C Stn Stn dig no -- -- RW
S1 Application S1A SCo nC doo no -- -- RW
S2 Application S2A nC nC doo no -- -- RW
S3 Application S3A nC nC doo no -- -- RW
DI Config diC dio doC dio no -- -- RW
DO1 Config o1C CoP CoP HEt no -- -- RW
DO2 Config o2C dEF 0 Lig no -- -- RW
DO3 Config o3C FAn 0 Lig no -- -- RW
DO4 Config o4C Lig 0 Lig no -- -- RW
Button 1 Short Config b1C noP tP noP no -- -- RW
Button 1 Long Config b1L PoF tP PoF no -- -- RW
Button 2 Short Config b2C dEF tP noP no -- -- RW
Button 3 Short Config b3C tP tP noP no -- -- RW
Button 3 Long Config b3L ECo tP PoF no -- -- RW
Button 4 Short Config b4C tn tP noP no -- -- RW
Button 4 Long Config b4L Lig tP PoF no -- -- RW
Pass-word level1 PS1 0 0 999 no RW RW RW
Pass-word level2 PS2 0 0 999 no -- RW RW
Pass-word level3 PS3 0 0 999 no -- -- RW
Cabinet Light Control
Source
CLC Lig Lig LEC no -- -- RW
Door close delay dCd 0 0 300 no Sec 1 -- -- RW
Light off delay Lod 0 0 300 no Sec 1 -- -- RW
Danfoss ERC 102
Hold 3 sec: Menu
1 Click: Variable direct function, e.g.ECO/Night mode
1 Click: Variable direct function, e.g. light
Sub function: Up
1 Click: Temperature setpoint
Sub function: Down
Sub function: Back
Sub function: OK
ERC Front and Button Functionallity:
1 Click: Temperature setpoint