EasyManuals Logo
Home>Danfoss>Controller>ERC 102

Danfoss ERC 102 User Manual

Danfoss ERC 102
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #26 background imageLoading...
Page #26 background image
26
Danfoss ERC 102
Hold 3 sec: Menu
1 Click: Variable direct function, e.g.ECO/Night mode
1 Click: Variable direct function, e.g. light
Sub function: Up
1 Click: Temperature setpoint
Sub function: Down
Sub function: Back
Sub function: OK
ERC Front and Button Functionallity:
1 Click: Temperature setpoint
7.2 Alarms / ALA
ERC menu
code
Default Min Max Unit
Conv
Unit Scale Default Access
Shop Ser OEM
Alarm ALA
High Alarm delay Htd 30 0 240 no min 1 -- RW RW
Low Alarm delay Ltd 0 0 240 no min 1 -- RW RW
High Temp Alarm HAt 15.0/59.0 -50.0/-58.0 80.0/176.0 C/Fa °C/°F .1 -- RW RW
Low Temp Alarm LAt -50.0/-58.0 -50.0/-58.0 80.0/176.0 C/F a °C/°F .1 -- RW RW
Pulldown delay Pdd 240 0 960 no min 1 -- RW RW
Door Open delay dod 2 0 60 no min 1 -- RW RW
Alarm Buzzer Duration Abd 0 0 999 no min 1 -- RW RW
Auto Clearance of
Alarm/Error
ACA yES no yES no 1 -- RW RW
ERC
102 Reference manual – 7 PARAMETERS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss ERC 102 and is the answer not in the manual?

Danfoss ERC 102 Specifications

General IconGeneral
BrandDanfoss
ModelERC 102
CategoryController
LanguageEnglish

Related product manuals