34
Fan Always On / FAo
If this parameter is set to yES, all other parameters in this section
about the fan are deactivated.
NOTE: If FAo is set to nO, then the following parameters will be applied.
Fan On Delay / Fod
Fan Stop Delay / FSd
If this parameter and FSd are both set to zero then the fan runs whenever the
compressor runs.
Fod defines the fan delay
(in seconds) after a compressor
cut-in.
FSd defines the fan delay after a
compressor cut-out.
7.5 Fan / FAn
ERC menu
code
Default Min Max Unit
Conv
Unit Scale Default Access
Shop Ser OEM
Fan FAn
Fan always On FAo yES no yES no 1 -- -- RW
Fan stop time on door open Fdt 999 0 999 no Sec 1 -- -- RW
Fan On Delay Fod 0 0 240 no Sec 1 -- -- RW
Fan Stop delay FSd 0 0 240 no Sec 1 -- -- RW
Fan On Cycle FoC 0 0 960 no Sec 1 -- -- RW
Fan Stop Cycle FSC 0 0 960 no Sec 1 -- -- RW
The fan parameters are all related to energy saving,
and to redistribution of air within the cabinet to
reduce the amount of energy spent on cooling.
Fan On Cycle / FoC
Fan Stop Cycle / FSC
When the compressor is off, and FoC or FSC are not zero, the fan runs in cycles
according to FoC and FSC.
Example: FoC = 120 [sec] and FSC = 120 [sec] means that the fan runs for half the
time when the compressor is off. When the compressor is on, the fan is always on
(according to FAo and Fod).
Danfoss ERC 102
Hold 3 sec: Menu
1 Click: Variable direct function, e.g.ECO/Night mode
1 Click: Variable direct function, e.g. light
Sub function: Up
1 Click: Temperature setpoint
Sub function: Down
Sub function: Back
Sub function: OK
ERC Front and Button Functionallity:
1 Click: Temperature setpoint
Danfoss ERC 102
Hold 3 sec: Menu
1 Click: Variable direct function, e.g.ECO/Night mode
1 Click: Variable direct function, e.g. light
Sub function: Up
1 Click: Temperature setpoint
Sub function: Down
Sub function: Back
Sub function: OK
ERC Front and Button Functionallity:
1 Click: Temperature setpoint
Danfoss ERC 102
Hold 3 sec: Menu
1 Click: Variable direct function, e.g.ECO/Night mode
1 Click: Variable direct function, e.g. light
Sub function: Up
1 Click: Temperature setpoint
Sub function: Down
Sub function: Back
Sub function: OK
ERC Front and Button Functionallity:
1 Click: Temperature setpoint
Danfoss ERC 102
Hold 3 sec: Menu
1 Click: Variable direct function, e.g.ECO/Night mode
1 Click: Variable direct function, e.g. light
Sub function: Up
1 Click: Temperature setpoint
Sub function: Down
Sub function: Back
Sub function: OK
ERC Front and Button Functionallity:
1 Click: Temperature setpoint
Danfoss ERC 102
Hold 3 sec: Menu
1 Click: Variable direct function, e.g.ECO/Night mode
1 Click: Variable direct function, e.g. light
Sub function: Up
1 Click: Temperature setpoint
Sub function: Down
Sub function: Back
Sub function: OK
ERC Front and Button Functionallity:
1 Click: Temperature setpoint
Danfoss ERC 102
Hold 3 sec: Menu
1 Click: Variable direct function, e.g.ECO/Night mode
1 Click: Variable direct function, e.g. light
Sub function: Up
1 Click: Temperature setpoint
Sub function: Down
Sub function: Back
Sub function: OK
ERC Front and Button Functionallity:
1 Click: Temperature setpoint
ERC
102 Reference manual – 7 PARAMETERS
Fan stop time on door open: Fdt
The maximum time the fan will be stopped after the door has been opened.
0: fan will not stop under opening
1-998: number of seconds fan will be stopped during door opening
999: fan will be stopped as long as the door is open
Danfoss ERC 102
Hold 3 sec: Menu
1 Click: Variable direct function, e.g.ECO/Night mode
1 Click: Variable direct function, e.g. light
Sub function: Up
1 Click: Temperature setpoint
Sub function: Down
Sub function: Back
Sub function: OK
ERC Front and Button Functionallity:
1 Click: Temperature setpoint