33
Fan Delay after Defrost / Fdd
This parameter can be set to between 0 and 60 seconds and defines how
long the delay is between the start of the compressor after defrost
and the
fan starting again.
Fan Start Temperature / Ftd
This only applies if an evaporator temperature sensor is fitted. This parameter
determines at what evaporator temperature the fan will start after a defrost cycle
is complete.
If the time set in Fdd occurs before the temperature set in Ftd, the fan will start
in line with Fdd. If the temperature set in Ftd occurs first, then the fan will start in
line with Ftd. It is therefore a case of whichever parameter’s setting is reached first
which determines when the fan starts.
Defrost Fan On / dFA
Set to yES, the fan will constantly run during defrost cycles.
Set to nO, the fan will not run during defrost cycles.
Initial Defrost Interval / idi
The initial defrost interval determines the time for first defrost after power-up. The
initial defrost is mainly intended for factory testing of the defrost functionality and
can be set to expire after a number compressor cycles according to the setting
of parameter idd . During normal operation, the defrost counter will be saved in
memory and restored after power loss, making the initial defrost unnecessary.
Defrost On Compressor Time / dCt
If this parameter is set to yES, then defrost cycles are based on the total time
the compressor has been running.
If this parameter is set to nO, then defrost cycles are related to elapsed time,
regardless of how long and how often the compressor has been on.
Danfoss ERC 102
Hold 3 sec: Menu
1 Click: Variable direct function, e.g.ECO/Night mode
1 Click: Variable direct function, e.g. light
Sub function: Up
1 Click: Temperature setpoint
Sub function: Down
Sub function: Back
Sub function: OK
ERC Front and Button Functionallity:
1 Click: Temperature setpoint
Danfoss ERC 102
Hold 3 sec: Menu
1 Click: Variable direct function, e.g.ECO/Night mode
1 Click: Variable direct function, e.g. light
Sub function: Up
1 Click: Temperature setpoint
Sub function: Down
Sub function: Back
Sub function: OK
ERC Front and Button Functionallity:
1 Click: Temperature setpoint
Danfoss ERC 102
Hold 3 sec: Menu
1 Click: Variable direct function, e.g.ECO/Night mode
1 Click: Variable direct function, e.g. light
Sub function: Up
1 Click: Temperature setpoint
Sub function: Down
Sub function: Back
Sub function: OK
ERC Front and Button Functionallity:
1 Click: Temperature setpoint
Danfoss ERC 102
Hold 3 sec: Menu
1 Click: Variable direct function, e.g.ECO/Night mode
1 Click: Variable direct function, e.g. light
Sub function: Up
1 Click: Temperature setpoint
Sub function: Down
Sub function: Back
Sub function: OK
ERC Front and Button Functionallity:
1 Click: Temperature setpoint
Danfoss ERC 102
Hold 3 sec: Menu
1 Click: Variable direct function, e.g.ECO/Night mode
1 Click: Variable direct function, e.g. light
Sub function: Up
1 Click: Temperature setpoint
Sub function: Down
Sub function: Back
Sub function: OK
ERC Front and Button Functionallity:
1 Click: Temperature setpoint
ERC
102 Reference manual – 7 PARAMETERS
Initial Defrost Duration / idd
The initial defrost duration is the number of compressor cycles before the initial
defrost is deactivated.
0: idi No initial defrost
1-998: number of compressor cycles before deactivation
999: Initial defrost always active.
Danfoss ERC 102
Hold 3 sec: Menu
1 Click: Variable direct function, e.g.ECO/Night mode
1 Click: Variable direct function, e.g. light
Sub function: Up
1 Click: Temperature setpoint
Sub function: Down
Sub function: Back
Sub function: OK
ERC Front and Button Functionallity:
1 Click: Temperature setpoint