VLT
®
5000 FLUX
514 Bus time interval function
(BUS TIMEOUT FUNC)
Value:
Off (OFF)
[0]
Freeze output (FREEZE OUTPUT)
[1]
Stop (STOP)
[2]
Jogging (JOGGING)
[3]
Max. speed (MAX SPEED)
[4]
Stop and trip (STOP AND TRIP)
[5]
Function:
This parameter selects the desired reaction of the
frequency converter when the set time for bus timeout
(parameter 513) has been exceeded.
If choices [1] to [5] are activated, relay 01 and
relay 04 will be de-activated.
Ifmoretime-outsoccuratthesametimethe
frequency converter will give the following priority
to the time-out function:
1. Parameter 318 Function after time out
2. Parameter 346 Function after encoder loss
3. Parameter 514 Bus time interval function.
Description of choice:
The output frequency of the frequency converter
can: be frozen at the present value, be frozen at
the reference, go to stop, go to jogging speed
(parameter 213), go to max. output speed (parameter
202) or stop and activate a trip.
Parameter
no.
Description Display
text
Unit Updating
interval
515 Reference % (REFERENCE) % 80 msec.
516 Reference Unit (REFERENCE [UNIT]) Hz, Nm or rpm 80 msec.
518 Frequency (FREQUENCY) Hz 80 msec.
520 Current (MOTOR CURRENT) Amp 80 msec.
521 Torque (TORQUE) % 80 msec.
522 Power, kW (POWER (KW) kW 80 msec.
523 Power, HP (POWER (HP) HP (US) 80 msec.
524 Motor voltage (MOTOR VOLTAGE) V 80 msec.
525 DC link voltage (DC LNK VOLTAGE) V 80 msec.
526 Motor temp. (MOTOR THERMAL) % 80 msec.
527 VLT temp. (VLT THERMAL) % 80 msec.
528 Digital input (DIGITAL INPUT) Binary code 2 msec.
529 Terminal 53, analog
input
(ANALOG INPUT 53) V 20 msec.
530 Terminal 54, analog
input
(ANALOG INPUT 54) V 20 msec.
531 Terminal 60, analog
input
(ANALOG INPUT 60) mA 20 msec.
532 Pulse reference (PULSE REFERENCE) Hz 20 msec.
533 External reference % (EXT. REFERENCE) % 20 msec.
534 Status word (STATUS WORD [HEX]) Hex code 20 msec.
535 Brake power/2 min. (BR. ENERGY/2 MIN) kW
536 Brake power/sec. (BRAKE ENERGY/S) kW
537 Heat sink temperature (HEATSINK TEMP.) °C 1.2 sec.
538 Alarm word (ALARM WORD [HEX]) Hex code 20 msec.
539 VLT control word (CONTROLWORD [HEX]) Hex code 2 msec.
540 Warning word, 1 (WARN. WORD 1) Hex code 20 msec.
541 Extended status word
Hex
(EXT. STATUS WORD) Hex code 20 msec.
557 Motor RPM (MOTOR RPM) RPM 80 msec.
558 Motor RPM x scaling (MOTOR RPM X SCALE) - 80 msec.
Function:
These parameters can be read out via the serial
communication port and via the display in Display
mode, see also parameters 009 - 012.
Description of choice:
Reference %, parameter 515:
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.55.A6.02 - VLT is a registered Danfoss trademark
112