■ Analog Outputs
Analog outputs (terminal 42 and 45).
Analog outputs are current outputs: 0/4 - 20 mA.
Common terminal (terminal 39) is the same terminal and electrical potential for analog common and digital
common connection.
Outputs terminal no. 42 45
parameter 319 321
Value:
No function (NO OPERATION) [0]✭ [0]✭
0-100 Hz ⇒ 0-20 mA (0-100 Hz = 0-20 mA) [1] [1]
0-100 Hz ⇒ 4-20 mA (0-100 Hz = 4-20 mA) [2] [2]
Ref
MIN
-Ref
MAX
⇒ 0-20 mA (REF MIN-MAX = 0-20 mA) [3] [3]
Ref
MIN
-Ref
MAX
⇒ 4-20 mA (REF MIN-MAX = 4-20 mA) [4] [4]
0-I
MAX
⇒ 0-20 mA (0-IMAX = 0-20 mA) [7] [7]
0-I
MAX
⇒ 4-20 mA (0-IMAX = 4-20 mA) [8] [8]
0-T
LIM
⇒ 0-20 mA (0-TLIM = 0-20 mA) [9] [9]
0-T
LIM
⇒ 4-20 mA (0-TLIM = 4-20 mA) [10] [10]
0-T
NOM
⇒ 0-20 mA (0-TNOM = 0-20 mA) [11] [11]
0-T
NOM
⇒ 4-20 mA (0-TNOM = 4-20 mA) [12] [12]
0-P
NOM
⇒ 0-20 mA (0-PNOM = 0-20 mA) [13] [13]
0-P
NOM
⇒ 4-20 mA (0-PNOM = 4-20 mA) [14] [14]
0 - MAX SPEED ⇒ 0-20 mA (0-MAX SPD. = 0-20 mA) [15] [15]
0 - MAX SPEED ⇒ 4-20 mA (0-MAX SPD. = 4-20 mA) [16] [16]
+/-160% TORQ ⇒ 0-20mA (+/-160% TORQ= 0-20mA) [17] [17]
+/-160% TORQ ⇒ 4-20mA (+/-160% TORQ= 4-20mA) [18] [18]
319 Terminal 42 Output
(AO 42 FUNCTION)
Value:
See tabel in section Analog Outputs.
Function:
The analog output function generates an
analog current 0/4-20 mA.
Description of choice:
See description in section Analog output.
321 Terminal 45, output
(AO 45 FUNCTION)
Value:
See table in section Analog outputs.
Function:
The analog output function generates an
analog current 0/4-20 mA.
Description of choice:
See description in section Analog O utputs .
✭ = factory setting. () = display text [] = value for use in communication via serial communication port
MG.55.A6.02 - VLT is a registered Danfoss trademark