Parameter group 3xx selects the analog and digital inputs and outputs to the desired function. Also scaling of
the inputs and outputs is performed in this group. Inputs: Max frequency on inputs terminal 16, 17, 18, 19,
27, 32, and 33 is 5 kHz. (24Vpp). Max frequency on inputs terminal 29 is 65 kHz (24Vpp).
Max frequency for the encoder inputs terminal 73 - 78 is 250 kHz (5Vpp). Outputs: Analog outputs terminal
42 and 45 are scaleable current outputs. Max frequency on digital outputs terminal 26 and 46 is 50kHz.
PNU Parameter Factory setting Range Changes 4-Setup
Conver-
sion Data
# description during operation index type
300 Terminal 16, input Reset Yes Yes 0 5
301 Terminal 17, input Freeze reference Yes Yes 0 5
302 Terminal 18 Start, input Start Yes Yes 0 5
303 Terminal 19, input Reversing Yes Yes 0 5
304 Terminal 27, input Coasting stop, inverse Yes Yes 0 5
305 Terminal 29, input Jog Yes Yes 0 5
306 Terminal 32, input Choice of setup, msb/speed up Yes Yes 0 5
307 Terminal 33, input Choice of setup, lsb/speed down Yes Yes 0 5
308 Terminal 53, analog input voltage Reference Yes Yes 0 5
309 Terminal 53, min. scaling 0.0 V 0.0 - 10.0 V Yes Yes -1 5
310 Terminal 53, max. scaling 10.0 V 0.0 - 10.0 V Yes Yes -1 5
311 Terminal 54, analog input voltage No operation Yes Yes 0 5
312 Terminal 54, min. scaling 0.0 V 0.0 - 10.0 V Yes Yes -1 5
313 Terminal 54, max. scaling 10.0 V 0.0 - 10.0 V Yes Yes -1 5
314 Terminal 60, analog input current Reference Yes Yes 0 5
315 Terminal 60, min. scaling 0.0 mA 0.0 - 20.0 mA Yes Yes -4 5
316 Terminal 60, max. scaling 20.0 mA 0.0 - 20.0 mA Yes Yes -4 5
317 Time out 10 sec. 0 - 99 sec. Yes Yes 0 5
318 Function after time out Off Yes Yes 0 5
319 Terminal 42, output 0-n
MAX
0-20 mA Yes Yes 0 5
321 Terminal 45, output 0-n
MAX
0-20 mA Yes Yes 0 5
323 Relay 01, output No operation Yes Yes 0 5
324 Relay 01, ON delay 0.00 sec. 0.00 - 600.00 sec. Yes Yes -2 6
325 Relay 01, OFF delay 0.00 sec. 0.00 - 600.00 sec. Yes Yes -2 6
326 Relay 04, output No operation Yes Yes 0 5
327 Pulse reference, max. frequency 100 - 65000 Hz 5000 Hz Yes Yes 0 6
329 Encoder feedback pulse/rev. 1024 pulses/rev. 500 - 10.000 pulses/rev. Yes Yes 0 6
341 Terminal 46, digital output No operation Yes Yes 0 5
342 Terminal 46, output, pulse scaling 5000 Hz 1 - 50000 Hz Yes Yes 0 6
350 Encoder monitoring OFF No No 0 5
351 Encoder direction Normal No Yes 0 5
355 Terminal 26, digital output No operation Yes Yes 0 5
356 Terminal 26, output, pulse scaling 5000 Hz 1 - 50000 Hz Yes Yes 0 6
357 Terminal 42, Output minimum scaling 0 % 000 - 100% Yes Yes 0 6
358 Terminal 42, Output maximum scaling 100% 000 - 500% Yes Yes 0 6
359 Terminal 45, Output minimum scaling 0 % 000 - 100% Yes Yes 0 6
360 Terminal 45, Output maximum scaling 100% 000 - 500% Yes Yes 0 6
361 Max Tracking Error OFF 000 - 999 rpm Yes Yes 0 6
362 KTY Sensor Type KTY1 KTY 1-3 No Yes 0 5
See also Operation and Display for further
information regarding Changes during operation,
4-Setup and Conversion index.
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.55.A6.02 - VLT is a registered Danfoss trademark
88