* Circuit Breakers manufactured by General Electric, Cat. No. SKHA36AT0800, with rating plugs listed below
can be used to meet UL-requirements:
5122 rating plug No. SRPK800 A 300
5152 rating plug No. SRPK800 A 400
5202 rating plug No. SRPK800 A 400
5252 rating plug No. SRPK800 A 500
5302 rating plug No. SRPK800 A 600
KTS-fuses from Bussmann may substitute KTN for 240 V drives.
FWH-fuses from Bussmann may substitute FWX for 240 V drives.
KLSR fuses from LITTEL FUSE may substitute KLNR fuses for 240 V drives.
L50S fuses from LITTEL FUSE may substitute L50S fuses for 240 V drives.
A6KR fuses from FERRAZ SHAWMUT may substitute A2KR for 240 V drives.
A50X fuses from FERRAZ SHAWMUT may substitute A25X for 240 V drives.
NonULcompliance
If UL/cUL is not to be complied with, we recommend the above mentioned fuses or:
VLT 5001-5027 200-240 V type gG
VLT 5001-5062 380-500 V type gG
VLT 5032-5052 200-240 V type gR
VLT 5072-5500 380-500 V type gR
Not following the recommendation may result
in unnecessary damage of the drive in case of
malfunction. Fuses must be designed for protection in
a circuit capable of supplying a maximum of 100000
A
rms
(symmetrical), 500/600 V maximum.