VLT
®
5000 FLUX
Programming
selected. A logic ‘1‘ on the terminal selected for speed
up, the reference or the output speed will increase.
A logic ‘1‘ on the terminal selected for speed down, the
reference or the output frequency will be reduced.
Pulses (logic ‘1‘ minimum high for 3 ms and a
minimum pause of 3 ms) will change the speed of
0.1% (reference) or 1 rpm (output speed).
If Speed up/Speed down is activated for more than 400
msec., a continuous change using ramp 2 will begin.
Example:
Terminal Freeze ref./
(16) (17) Freeze output
No speed change 0 0 1
Speed down 0 1 1
Speed up 1 0 1
Speed down 1 1 1
The speed reference frozen via the control panel
can be changed even if the frequency converter
has stopped. The frozen ref
erence will be stored
in case of a mains cut-out.
Choice of Setup LSB and MSB enables one of the
four Setups; however, this depends on the fact that
parameter 004 has b
een set to Multi S etup.
Choice of Setup M
SB/Speed up and choice
of Setup LSB/Speed down - In conjunction
with Freeze reference or Freeze output -enable
up/down spee
d change.
The selecti
on of Setup changes in accordance
with the below table:
Selection of Setup Freeze ref/
(32)msb (33)lsb Freeze output
Setup 1 0 0 0
Setup 2 0 1 0
Setup 3 1 0 0
Setup 4 1 1 0
No speed change 0 0 1
Speed down 0 1 1
Speed up 1 0 1
Speed down 1 1 1
Catch-up/Slow-down is selected if the reference
value is to be increased or reduced by a programmable
percentage value set in parameter 219.
Slow-down Catch-up
Unchanged speed 0 0
Reduced by %-value 1 0
Increased by %-value 0 1
Reduced by %-value 1 1
Ramp 2 is selected if a change between ramp 1
(parameters 207-208) and ramp 2 (209-210) is desired.
Logic 0 ramp 1, while logic 1 ramp 2.
Mains failure inverted is to be selected if parameter
407 Mai n s failure and/or parameter 408 Quick
discharge is activated. Mains failure inverted is
active in the logical ‘0 situation.
NB!:
The frequency converter can be totally
damaged by repeating the Quick discharge
function on the digital input with mains
voltage connected to the drive.
Pulse reference is selected if a pulse sequence
(speed) of 0 rpm is used, corresponding to Ref
MIN
,
parameter 204. The frequency is set in parameter
327, corresponding to Ref
MAX
.
Parameter no. Description Display text Max frequency to terminal
300 Terminal 16, input (DIGITAL INPUT 16) 5 kHz.
301 Terminal 17, input (DIGITAL INPUT 17) 5 kHz.
302 Terminal 18 Start, input (DIGITAL INPUT 18) 5 kHz.
303 Terminal 19, input (DIGITAL INPUT 19) 5 kHz.
304 Terminal 27, input (DIGITAL INPUT 27) 5 kHz.
305 Terminal 29, input (DIGITAL INPUT 29) 65 kHz.
306 Terminal 32, input (DIGITAL INPUT 32) 5 kHz.
307 Terminal 33, input (DIGITAL INPUT 33) 5 kHz.
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.55.A6.02 - VLT is a registered Danfoss trademark
91

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 5000 FLUX and is the answer not in the manual?

Danfoss VLT 5000 FLUX Specifications

General IconGeneral
BrandDanfoss
ModelVLT 5000 FLUX
CategoryDC Drives
LanguageEnglish

Related product manuals