VLT
®
6000 HVAC Series
Installation
Technical data, mains supply 3x380-460V
According to international requirements VLT type 6152 6172 6222 6272 6352
I
VLT,N
[A] (380-440 V) 212 260 315 395 480
Output current
I
VLT, MAX
(60 s) [A]
(380-440 V)
233 286 347 435 528
I
VLT,N
[A] (441-460 V) 190 240 302 361 443
I
VLT, MAX
(60 s) [A]
(441-460 V)
209 264 332 397 487
S
VLT,N
[kVA] (400 V) 147 180 218 274 333
Output power
S
VLT,N
[kVA] (460 V) 151 191 241 288 353
Typical shaft output (380-440 V) P
VLT,N
[kW] 110 132 160 200 250
Typical shaft output (441-460 V) P
VLT,N
[HP] 150 200 250 300 350
Max. cable cross-section to motor and DC-bus
[mm
2
]
2) 4) 5)
2x70 2x70 2x185 2x185 2x185
Max. cable cross-section to motor and DC-bus
[AWG]
2) 4) 5)
2x2/0
mcm
2x2/0
mcm
2x350
mcm
2x350
mcm
2x350
mcm
Min. cable cross-section to motor and DC-bus
[mm
2
/AWG]
2) 4) 5)
35/2 35/2 35/2 35/2 35/2
I
L,N
[A] (380 V) 208 256 317 385 467Max. input current
(RMS)
I
L,N
[A] (460 V) 185 236 304 356 431
Max. cable cross-section to power [mm
2
]
2) 4) 5)
2x70 2x70 2x185 2x185 2x185
Max. cable cross-section to power [AWG]
2) 4) 5)
2x2/0
mcm
2x2/0
mcm
2x350
mcm
2x350
mcm
2x350
mcm
Max. pre-fuses [-]/UL
1)
[A] 300/300 350/350 450/400 500/500 630/600
Weight IP 00 [kg] 82 91 112 123 138
Weight IP 20 [kg] 96 104 125 136 151
Weight IP 54 [kg] 96 104 125 136 151
Efficiency at rated frequency 0.98
Power loss at max.
load.
[W] 2619 3309 4163 4977 6107
Enclosure IP 00/IP 21/NEMA 1/IP 54
1. For type of fuse, see section Fuses.
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
4. Min. cable cross-section is the smallest cable cross-section allowed to be fitted on the terminals. Max. cable
cross section is the maximum possible cable cross section that can be fitted on the terminals.
Always comply with national and local regulations on min. cable cross-section.
5. Connection bolt 1 x M10 / 2 x M10 (mains and motor), connection bolt 1 x M8 / 2 x M8 (DC-bus).
MG.61.A5.02 - VLT is a registered Danfoss trademark
31

Table of Contents

Other manuals for Danfoss VLT 6000 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 6000 series and is the answer not in the manual?

Danfoss VLT 6000 series Specifications

General IconGeneral
BrandDanfoss
ModelVLT 6000 series
CategoryMedia Converter
LanguageEnglish

Related product manuals