VLT
®
6000 HVAC Series
■ Technical data, mains supply 3 x 380-460 V
According to international requirements VLT type 6402 6502 6552 6602
Output current I
VLT,N
[A] (380-440 V) 600 658 745 800
I
VLT, MAX
(60 s) [A] (380-440 V) 660 724 820 880
I
VLT,N
[A] (441-460 V) 540 590 678 730
I
VLT, MAX
(60 s) [A] (441-460 V) 594 649 746 803
Output power S
VLT,N
[kVA] (400 V) 416 456 516 554
S
VLT,N
[kVA] (460 V) 430 470 540 582
Typical shaft output (380-440 V) P
VLT,N
[kW] 315 355 400 450
Typical shaft output (441-460 V) P
VLT,N
[HP] 450 500 550/600 600
Max. cable cross-section to motor and DC-bus
[mm
2
]
4) 5)
4 x 240 4 x 240 4 x 240 4 x 240
Max. cable cross-section to motor and DC-bus
[AWG]
2) 4) 5)
4 x 500 mcm 4 x 500 mcm 4 x 500 mcm 4 x 500 mcm
I
L,MAX
[A] (380 V) 584 648 734 787Max. input
current (RMS) I
L,MAX
[A] (460 V) 526 581 668 718
Max. cable cross-section to power [mm
2
]
4) 5)
4 x 240 4 x 240 4 x 240 4 x 240
Max. cable cross-section to power [AWG]
2) 4) 5)
4 x 500 mcm 4 x 500 mcm 4 x 500 mcm 4 x 500 mcm
Max. pre-fuses
(mains) [-]/UL [A]
1)
700/700 900/900 900/900 900/900
Efficiency
3)
0.98 0.98 0.98 0.98
Weight IP 00 [kg] 221 234 236 277
Weight IP 20 [kg] 263 270 272 313
Weight IP 54 [kg] 263 270 272 313
Power loss at
max. load [W] 7630 7701 8879 9428
Enclosure IP 00 / IP 21/NEMA 1 / IP 54
1. Fortypeoffuse,seesectionFuses.
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
4. Always comply with national and local regulations on min. cable cross-section. Max. cable cross
section is the maximum possible cable cross section that can be fitted on the terminals.
5. Connection bolt power supply, motor and load sharing: M10 compression (lug), 2 x M8 (box lug)
MG.61.A5.02 - VLT is a registered Danfoss trademark