Enclosure Type C1 C2 C3 C4 D3h
Power
[kW]
200-240 V 15-22 30-37 18.5-22 30-37
-
380-480/500 V 30-45 55-75 37-45 55-75
-
525-600 V 30-45 55-90 37-45 55-90
-
525-690 V 30-75 37-45 55-75
Illustrations
IP 21/55/66 21/55/66 20 20 20
NEMA Type 1/12/4X Type 1/12/4X Chassis Chassis Chassis
Height [mm]
Height of back plate A 680 770 550 660 909
Height with de-coupling plate for
Fieldbus cables
A - - 630 800 -
Distance between mounting holes a 648 739 521 631 -
Width [mm]
Width of back plate B 308 370 308 370 250
Width of back plate with one C
option
B 308 370 308 370 -
Width of back plate with 2 C
options
B 308 370 308 370 -
Distance between mounting holes b 272 334 270 330 -
Depth [mm]
Depth without option A/B C 310 335 333 333 275
With option A/B C 310 335 333 333 275
Screw holes [mm]
c 12.5 12.5 - - -
d ø19 ø19 - - -
e ø9 ø9 8.5 8.5 -
f 9.8 9.8 17 17 -
Max weight [kg]
45 65 35 50 62
Front cover tightening torque [Nm]
Plastic cover (low IP) Click Click 2.0 2.0 -
Metal cover (IP55/66) 2.2 2.2 2.0 2.0 -
Illustration 8.1 Top and Bottom Mounting Holes (B4, C3
and C4 only)
Table 8.2 Mechanical Dimensions, Enclosure Types C and D
NOTICE
Accessory bags containing necessary brackets, screws and connectors are shipped with the frequency converters upon
delivery.
Mechanical Installation
VLT
®
AutomationDrive FC 301/FC 302 Design Guide, 0.25-75 kW
MG33BF02 - Rev. 2013-12-20 109
8 8