requested action, the follower constructs an error message,
and send it in response, or a time-out occurs.
12.9.4 Frequency Converter with Modbus
RTU
The frequency converter communicates in Modbus RTU
format over the built-in RS-485 interface. Modbus RTU
provides access to the control word and bus reference of
the frequency converter.
The control word allows the modbus master to control
several important functions of the frequency converter:
Start
Stop of the frequency converter in various ways:
-
Coast stop
-
Quick stop
-
DC Brake stop
-
Normal (ramp) stop
Reset after a fault trip
Run at a variety of preset speeds
Run in reverse
Change the active set-up
Control the frequency converter’s built-in relay
The bus reference is commonly used for speed control. It is
also possible to access the parameters, read their values,
and where possible, write values to them. This permits a
range of control options, including controlling the setpoint
of the frequency converter when its internal PI controller is
used.
12.10
Network Configuration
To enable Modbus RTU on the frequency converter, set the
following parameters
Parameter Setting
8-30 Protocol Modbus RTU
8-31 Address 1-247
8-32 Baud Rate 2400-115200
8-33 Parity / Stop Bits Even parity, 1 stop bit (default)
Table 12.10 Modbus RTU Parameters
12.11
Modbus RTU Message Framing
Structure
12.11.1 Frequency Converter with Modbus
RTU
The controllers are set up to communicate on the Modbus
network using RTU (Remote Terminal Unit) mode, with
each byte in a message containing 2 4-bit hexadecimal
characters. The format for each byte is shown in
Table 12.11.
Start
bit
Data byte Stop/
parity
Stop
Table 12.11 Format for Each Byte
Coding System 8-bit binary, hexadecimal 0-9, A-F. 2
hexadecimal characters contained in each 8-
bit field of the message
Bits Per Byte 1 start bit
8 data bits, least significant bit sent first
1 bit for even/odd parity; no bit for no
parity
1 stop bit if parity is used; 2 bits if no parity
Error Check Field Cyclical Redundancy Check (CRC)
12.11.2 Modbus RTU Message Structure
The transmitting device places a Modbus RTU message
into a frame with a known beginning and ending point.
This allows receiving devices to begin at the start of the
message, read the address portion, determine which
device is addressed (or all devices, if the message is
broadcast), and to recognise when the message is
completed. Partial messages are detected and errors set as
a result. Characters for transmission must be in
hexadecimal 00 to FF format in each field. The frequency
converter continuously monitors the network bus, also
during ‘silent’ intervals. When the first field (the address
field) is received, each frequency converter or device
decodes it to determine which device is being addressed.
Modbus RTU messages addressed to zero are broadcast
messages. No response is permitted for broadcast
messages. A typical message frame is shown in Table 12.12.
Start Address Function Data CRC
check
End
T1-T2-T3-
T4
8 bits 8 bits N x 8
bits
16 bits T1-T2-T3-
T4
Table 12.12 Typical Modbus RTU Message Structure
RS-485 Installation and Set...
VLT
®
AutomationDrive FC 301/FC 302 Design Guide, 0.25-75 kW
MG33BF02 - Rev. 2013-12-20 183
12 12

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 301

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 301 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 301 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 301
CategoryDC Drives
LanguageEnglish

Related product manuals