6.2 General Specifications
6.2.1 Mains Supply
Mains supply
Supply Terminals (6-Pulse) L1, L2, L3
Supply voltage 200-240 V ±10%
Supply voltage FC 301: 380-480 V/FC 302: 380-500 V ±10%
Supply voltage FC 302: 525-600 V ±10%
Supply voltage FC 302: 525-690 V ±10%
Mains voltage low/mains drop-out:
During low mains voltage or a mains drop-out, the frequency converter continues until the intermediate circuit voltage drops
below the minimum stop level, which corresponds typically to 15% below the frequency converter's lowest rated supply voltage.
Power-up and full torque cannot be expected at mains voltage lower than 10% below the frequency converter's lowest rated
supply voltage.
Supply frequency 50/60 Hz ±5%
Max. imbalance temporary between mains phases 3.0 % of rated supply voltage
True Power Factor (λ) 0.9 nominal at rated load
Displacement Power Factor (cos ϕ) near unity (> 0.98)
Switching on input supply L1, L2, L3 (power-ups) 7.5 kW maximum 2 times/min.
Switching on input supply L1, L2, L3 (power-ups) 11-75 kW maximum 1 time/min.
Switching on input supply L1, L2, L3 (power-ups) 90 kW maximum 1 time/2 min.
Environment according to EN60664-1 overvoltage category III/pollution degree 2
The unit is suitable for use on a circuit capable of delivering not more than 100,000 RMS symmetrical Amperes, 240/500/600/690
V maximum.
6.2.2
Motor Output and Motor Data
Motor output (U, V, W)
Output voltage 0-100% of supply voltage
Output frequency 0-590 Hz
3)
Output frequency in Flux Mode 0-300 Hz
Switching on output Unlimited
Ramp times 0.01-3600 s
Torque characteristics
Starting torque (constant torque) maximum 160% for 60 s
1)
once in 10 min.
Starting/overload torque (variable torque) maximum 110% up to 0.5 s
1)
once in 10 min.
Torque rise time in FLUX (for 5 kHz fsw) 1 ms
Torque rise time in VVC
+
(independent of fsw) 10 ms
1) Percentage relates to the nominal torque.
2) The torque response time depends on application and load but as a general rule, the torque step from 0 to reference is 4-5 x
torque rise time.
3) Special customer versions with output frequency 0-1000 Hz are available.
Product Specifications
VLT
®
AutomationDrive FC 301/FC 302 Design Guide, 0.25-75 kW
68 MG33BF02 - Rev. 2013-12-20
66

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 301

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 301 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 301 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 301
CategoryDC Drives
LanguageEnglish

Related product manuals