Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
R1R2
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
01
02
03
04
05
06
130BB839.10
Function Setting
4-30 Motor
Feedback Loss
Function
[1] Warning
4-31 Motor
Feedback Speed
Error
100 RPM
4-32 Motor
Feedback Loss
Timeout
5 s
7-00 Speed PID
Feedback Source
[2] MCB 102
17-11 Resolution
(PPR)
1024*
13-00 SL
Controller Mode
[1] On
13-01 Start
Event
[19] Warning
13-02 Stop
Event
[44] Reset
key
13-10 Comparat
or Operand
[21] Warning
no.
13-11 Comparat
or Operator
[1] ≈*
13-12 Comparat
or Value
90
13-51 SL
Controller Event
[22]
Comparator 0
13-52 SL
Controller Action
[32] Set
digital out A
low
5-40 Function
Relay
[80] SL digital
output A
*=Default Value
Notes/comments:
If the limit in the feedback
monitor is exceeded, Warning
90 is issued. The SLC monitors
Warning 90 and in the case
that Warning 90 becomes TRUE
then relay 1 is triggered.
External equipment may
indicate that service is required.
If the feedback error goes
below the limit again within 5
s, the frequency converter
continues and the warning
disappears. But relay 1 is still
triggered until [Reset] on the
LCP.
Table 10.13 Using SLC to Set a Relay
Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
R1R2
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
01
02
03
04
05
06
130BB841.10
Function Setting
1-00 Configu-
ration Mode
[0] Speed
open loop
1-01 Motor
Control Principle
[1] VVC
+
5-40 Function
Relay
[32] Mech.
brake ctrl.
5-10 Terminal 18
Digital Input
[8] Start*
5-11 Terminal 19
Digital Input
[11] Start
reversing
1-71 Start Delay 0.2
1-72 Start
Function
[5] VVC
+
/
FLUX
Clockwise
1-76 Start
Current
I
m,n
2-20 Release
Brake Current
App.
dependent
2-21 Activate
Brake Speed
[RPM]
Half of
nominal slip
of the motor
*=Default Value
Notes/comments:
Table 10.14 Mechanical Brake Control (Open Loop)
Start (18)
Start
reversing (19)
Relay output
Speed
Time
Current
1-71
1-71
2-21
2-21
1-76
Open
Closed
130BB842.10
Illustration 10.4 Mechanical Brake Control (Open Loop)
Application Examples
VLT
®
AutomationDrive FC 301/FC 302 Design Guide, 0.25-75 kW
148 MG33BF02 - Rev. 2013-12-20
1010

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 301

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 301 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 301 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 301
CategoryDC Drives
LanguageEnglish

Related product manuals