Type Designation P30K P37K P45K P55K P75K
High/Normal Overload
1)
HO NO HO NO HO NO HO NO HO NO
Typical Shaft output [kW] 30 37 37 45 45 55 55 75 75 90
Enclosure IP21 C1 C1 C1 C2 C2
Enclosure IP20 B4 C3 C3 C4 C4
Enclosure IP55, IP66 C1 C1 C1 C2 C2
Output current
Continuous (380-440 V) [A] 61 73 73 90 90 106 106 147 147 177
Intermittent (60 s overload)
(380-440 V) [A]
91.5 80.3 110 99 135 117 159 162 221 195
Continuous (441-500 V) [A] 52 65 65 80 80 105 105 130 130 160
Intermittent (60 s overload)
(441-500 V) [A]
78 71.5 97.5 88 120 116 158 143 195 176
Continuous kVA (400 V) [kVA] 42.3 50.6 50.6 62.4 62.4 73.4 73.4 102 102 123
Continuous kVA (460 V) [kVA] 51.8 63.7 83.7 104 128
Max. input current
Continuous (380-440 V) [A] 55 66 66 82 82 96 96 133 133 161
Intermittent (60 s overload)
(380-440 V) [A]
82.5 72.6 99 90.2 123 106 144 146 200 177
Continuous (441-500 V) [A] 47 59 59 73 73 95 95 118 118 145
Intermittent (60 s overload)
(441-500 V) [A]
70.5 64.9 88.5 80.3 110 105 143 130 177 160
Additional specifications
IP20 max. cable cross-section for
mains and motor [mm
2
] ([AWG])
35 (2) 50 (1) 50 (1) 150 (300 MCM) 150 (300 MCM)
IP20 max. cable cross-section for
brake and load sharing [mm
2
]
([AWG])
35 (2) 50 (1) 50 (1) 95 (4/0) 95 (4/0)
IP21, IP55, IP66 max. cable cross-
section for mains and motor [mm
2
]
([AWG])
50 (1) 50 (1) 50 (1) 150 (300 MCM) 150 (300MCM)
IP21, IP55, IP66 max. cable cross-
section for brake and load sharing
[mm
2
] ([AWG])
50 (1) 50 (1) 50 (1) 95 (3/0) 95 (3/0)
Max cable cross-section
4)
for
mains disconnect [mm
2
] ([AWG])
50, 35, 35
(1, 2, 2)
95, 70, 70
(3/0, 2/0, 2/0)
185, 150, 120
(350 MCM, 300
MCM, 4/0)
Estimated power loss
at rated max. load [W]
3)
570 698 697 843 891 1083 1022 1384 1232 1474
Efficiency
2)
0.98 0.98 0.98 0.98 0.99
Table 6.6 Mains Supply 380-500 V (FC 302), 380-480 V (FC 301), P30K-P75K
Product Specifications
VLT
®
AutomationDrive FC 301/FC 302 Design Guide, 0.25-75 kW
62 MG33BF02 - Rev. 2013-12-20
66