Type Designation P11K P15K P18K P22K P30K
High/Normal Overload
1)
HO NO HO NO HO NO HO NO HO NO
Typical Shaft Output [kW] 11 15 15 18.5 18.5 22 22 30 30 37
Enclosure IP20 B3 B3 B4 B4 B4
Enclosure IP21, IP55, IP66 B1 B1 B2 B2 C1
Output current
Continuous (525-550 V) [A] 19 23 23 28 28 36 36 43 43 54
Intermittent (525-550 V) [A] 30 25 37 31 45 40 58 47 65 59
Continuous (551-600 V) [A] 18 22 22 27 27 34 34 41 41 52
Intermittent (551-600 V) [A] 29 24 35 30 43 37 54 45 62 57
Continuous kVA (550 V) [kVA] 18.1 21.9 21.9 26.7 26.7 34.3 34.3 41.0 41.0 51.4
Continuous kVA (575 V) [kVA] 17.9 21.9 21.9 26.9 26.9 33.9 33.9 40.8 40.8 51.8
Max. input current
Continuous at 550 V [A] 17.2 20.9 20.9 25.4 25.4 32.7 32.7 39 39 49
Intermittent at 550 V [A] 28 23 33 28 41 36 52 43 59 54
Continuous at 575 V [A] 16 20 20 24 24 31 31 37 37 47
Intermittent at 575 V [A] 26 22 32 27 39 34 50 41 56 52
Additional specifications
IP20 max. cable cross-section
4)
for
mains, brake, motor and load
sharing [mm
2
] ([AWG])
10, 10,- (8, 8,-) 10, 10,- (8, 8,-) 35,-,-(2,-,-) 35,-,-(2,-,-) 35,-,-(2,-,-)
IP21, IP55, IP66 max. cable cross-
section
4)
for mains, brake and load
sharing [mm
2
] ([AWG])
16, 10, 10 (6, 8, 8) 16, 10, 10 (6, 8, 8) 35,-,-(2,-,-) 35,-,-(2,-,-) 50,-,- (1,-,-)
IP21, IP55, IP66 max. cable cross-
section
4)
for motor [mm
2
] ([AWG])
10, 10,- (8, 8,-) 10, 10,- (8, 8,-) 35, 25, 25 (2, 4, 4) 35, 25, 25 (2, 4, 4) 50,-,- (1,-,-)
Max. cable cross-section
4)
for
Disconnect [mm
2
] ([AWG])
16, 10, 10
(6, 8, 8)
50, 35, 35
(1, 2, 2)
Estimated power loss
at rated max. load [W]
3)
220 300 300 370 370 440 440 600 600 740
Efficiency
2)
0.98 0.98 0.98 0.98 0.98
Table 6.8 Mains Supply 525-600 V (FC 302 only), P11K-P30K
Product Specifications
VLT
®
AutomationDrive FC 301/FC 302 Design Guide, 0.25-75 kW
64 MG33BF02 - Rev. 2013-12-20
66

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 301

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 301 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 301 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 301
CategoryDC Drives
LanguageEnglish

Related product manuals