Page #13 background image
E Protection response (parameter 36-2 Flow Sensor, parameter
36-6 High Flow, parameter 36-7 Low Flow, parameter 36-8 Flow
Switch)
2 Flow protection response delay (parameter 31-4 Flow
Response Delay)
Illustration 3: Operation - Flow Protection
6.3.1.1 Using an Analog 4–20 mA Sensor
Context:
An analog 4–20 mA sensor provides protection and monitoring.
Procedure
1. Connect the sensor to B33, B34.
2. Set parameter 30-5 Flow Sensor Type to Analog.
3. Set parameters 30-6 to 30-8 according to the sensor specifications.
4. Set parameters 31-1 to 31-4, parameter 36-2 Flow Sensor, and parameter 36-7 Low Flow as required.
6.3.1.2 Using a Switch Sensor
Context:
A switch sensor provides protection only.
Procedure
1. Connect the sensor to C23, C24.
2. Set parameter 30-5 Flow Sensor Type to Switch.
3. Set parameters 31-3 to 31-4, parameter 36-2 Flow Sensor, and parameter 36-8 Flow Switch as required.
Parameters 31-1 to 31-2 are not used with a switch sensor.
6.3.1.3 Using a Pulse Sensor
Context:
A pulse sensor provides protection and monitoring.
Procedure
1. Connect the sensor to C23, C24.
2. Set parameter 30-5 Flow Sensor Type to Pulses per Minute or Pulses per Unit.
3. Set parameter 30-6 Flow Units, 30-11 Units per Pulse, and either parameter 30-9 Units per Minute at Max Flow or parameter 30-10 Pulses
per Minute at Max Flow according to the sensor specifications.
4. Set parameters 31-1 to 31-4, and parameter 36-2 Flow Sensor, parameter 36-6 High Flow, and parameter 36-7 Low Flow as required.
Configuration
Installation Guide | Pumping Smart Card
AN279052730268en-000102 / 175R1183 | 13
Danfoss A/S © 2018.10

Table of Contents

Other manuals for Danfoss VLT MCD 600

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT MCD 600 and is the answer not in the manual?

Danfoss VLT MCD 600 Specifications

General IconGeneral
BrandDanfoss
ModelVLT MCD 600
CategoryController
LanguageEnglish

Related product manuals